Vitodens 200 WB2 Service
Diagnosis
With comfortrol menu driven progamming unit'
Faults with fault display on control unit
When a fault message is detected, –––– FAULT––––
flashes in the display of the programming unit with the
cover closed.
To trace the fault
1. Open cover:
FAULT SEARCH "A". Fault code is displayed.
Note: The fault message is cleared when
"ACKNOWLEDGE" is selected.
If an acknowledged fault is not corrected by
24:00 hrs on the same day, the fault message
will reappear.
The acoustic alarm system (only with optional
expansion board installed), is not reactivated.
The meaning of the fault codes is explained in
the table starting on page 28.
2. Close the cover.
To reset the burner
If red light is on or flashing:
1. Press the "EU" button once to reset the burner.
A Display window
B Reset button
C Burner fault indicator
Find nature of sensor fault in plain language
Note: Please refer to the diagnostics table starting on
page 28 for details on required action.
Open the cover:
Menu option
Button
MAIN MENU
"D"
SYSTEM
"D"
INSTALLER SETUP
"C"
CODE PLEASE:
"B-C-C-B"
DIAGNOSIS
"A"
SCAN SENSORS
"B"
Select defective sensor with the menu option
CONTINUE "A".
Troubleshooting
25