Start-up and Service
Check Functioning of Safety Valves
Check Electrical Connections
Check Gas Pipes and Fittings for Leaks
20
Ensure proper operation of low water cut-off(s)
(if applicable), pressure relief valve, and pump(s).
Check pressure gage, air vent and pressure relief valve.
Ensure that pressure relief valve does not leak and
that it operates in accordance with information provided
by the manufacturer.
Refer to maintenance instructions supplied with low water
cut-offs, pumps, etc.
Flush float water type low water cut-offs (if used).
Follow local regulations with respect to backflow
preventers.
If oil-lubricated pumps are used, ensure proper lubrication.
If motorized zone valves are used, refer to maintenance
instructions provided with zone valves.
Ensure all plug-in connectors and strain reliefs make
positive contact and are seated properly.
Installation Instructions Power Module
WARNING
The gas supply piping must be leak tested before placing
the boiler in operation.
CAUTION
Ensure all joints of gas line are pressure tight and that
gas valves do not leak when under normal operating
pressure (use approved leak detection liquid).
Vitodens 200 WB2 Service