WARNING
!
Use clean dry air
Do not use compressed air which contains chemicals, synthe c oils containing organic solvents, salts or corrosive gases, etc., as
this can cause damage or malfunc on.
CAUTION
!
Install air filter
Install air filters close to valves at their upstream side. A filtra on degree of 5 μm or less should be selected.
Install an air dryer, a er cooler or Drain Catch (water separator) etc.
Air that includes excessive moisture may cause malfunc on of valves and other pneuma c equipment. To prevent this, install
an air dryer, a er‐cooler, or water separator, etc.
If excessive carbon dust is generated
Eliminate it by installing mist separators at the upstream side of valves. If excessive carbon dust is generated by the
compressor, it may adhere to the inside of valves and cause malfunc on.
Control medium:
Dust content Quality class 7:
Water content Quality class 3:
Oil content
Quality class X:
Temperature range
of compressed air:
Pressure range:
Connec ons:
Fig. 5:
Solenoid operated air switch
The exhaust flow rates for both ports can be controlled separately to control the actuator speed in both energising and de‐
energising direc ons
Pg 20
Air, neutral gases
Quality classes in accordance with DIN ISO 8573‐1
(5µm filter recommended)
max. par cle size 40µm
max. par cle density 10mg/m³
max. pressure dew point –20°C or min. 10°C below the lowest opera ng temperature
max. 25mg/m³
‐10 ... +50° (non‐condensing)
3.0 ... 7 bar (minimum air pressure of system may be higher than minimum pressure to
operate solenoid, as required by product condi ons, valve or actuator)
6mm "One touch" push‐in fi ngs, collets and O‐rings are replaceable
F783E Ex‐ia
00‐ISN‐203_Rev B