Inspections And Maintenance; Instructions For Inspection And Maintenance - Alpha ARES 150 Tec Installation And Servicing Instructions

Floor standing, high output, modular condensing boilers
Table of Contents

Advertisement

Inspections and maintenance

4
INSPECTIONS AND
MAINTENANCE
Inspections and maintenance carried out to state of
the art and at regular intervals, as well as the exclusive
use of original spare parts, are of primary importance
for smooth operation and to guarantee long boiler life.
Annual maintenance of the appliance is compulsory, in
accordance with Legislation in force.
Failure to carry out Inspections and Maintenance can
cause material and personal damage.
4.1
INSTRUCTIONS FOR INSPECTION
AND MAINTENANCE
Only original Alpha Innovation spare parts must be used to ensure
a long life for all of the functions of your appliance, and to avoid
changing the conditions of the approved standard product. When a
part needs to be replaced:
• Disconnect the appliance from the mains power supply and make
sure it cannot be reconnected accidentally.
• Shut the gas cut-off valve upstream of the boiler.
• If necessary, and based on the work that needs to be carried out, close
any cut-off valves on the heating flow and return, as well as the cold
water inlet valve.
After completing all maintenance operations, restore the boiler's
operation.
• Open the heating flow and return, as well as the cold water inlet valve
(if it was previously closed).
• Relieve and, if necessary, restore the pressure in the heating system,
until reaching pressure of 0.8/1.0 bar.
• Open the gas cut-off valve.
• Apply voltage to the boiler.
• Make sure the appliance is water-tight, on the gas side and the water side.
Table of resistance values based on the heating probe (SR) and the heating return probe (SRR) temperature
T°C
0
0
32755
31137
10
20003
19072
20
12571
12019
30
8112
40
5363
50
3627
60
2504
70
1762
80
1263
90
920
Relation between the temperature (°C) and nom. resistance (Ohm) of the heating probe SR and the heating return probe SRR.
Example:
At 25°C, the nominal resistance is 10067 Ohm
1
2
3
29607
28161
18189
17351
11493
10994
7775
7454
7147
5152
4951
4758
3491
3362
3238
2415
2330
2249
1703
1646
1592
1222
1183
1146
892
865
839
OBLIGATION!
Wear protective gloves.
Scalding hazard!
Be careful during the maintenance operations.
4
5
6
26795
25502
24278
16557
15803
15088
10519
10067
9636
6855
6577
6311
4574
4398
4230
3119
3006
2897
2171
2096
2023
1539
1488
1440
1110
1075
1042
814
790
766
43
7
8
9
23121
22025
20987
14410
13765
13153
9227
8837
8466
6057
5815
5584
4069
3915
3768
2792
2692
2596
1954
1888
1824
1393
1348
1304
1010
979
949
744
722
701

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ares 200 tecAres 250 tecAres 300 tecAres 350 tec

Table of Contents