aci A/SCTE-50 Installation And Operation Instructions

aci A/SCTE-50 Installation And Operation Instructions

Advertisement

Quick Links

ACI
Automation Components, Inc.
 Safety
This product is not intended to be used for Life or Safety applications.
!
This product is not intended for use in any hazardous or classified locations.
Disconnect and lock out all power sources before installation as severe injury or death may result from electrical
shock due to contact with high voltage wires.
 Installation
Make sure that all installations are in compliance with all national and local electrical codes. Only qualified individuals that are
familiar with codes, standards, and proper safety procedures for high-voltage installations should attempt installation. The
current sensor will not require external power, since the power for the current sensor is induced from the conductor being
monitored.
The A/SCTE & A/SCTV Series Analog Current Sensors should be used on Insulated Conductors Only! The current sensors may
be mounted in any position using the (2) #8 x 3/4" Tek screws and the mounting holes in the base or snapped directly onto the
35mm DIN rail (See Figures 1 & 2 below). Leave a minimum distance of 1" (3 cm) between the current
sensor and any other magnetic devices such as contactors and transformers.
 Latch Operation:
Pressing down on the two (2) side tabs and swinging the cover open opens the split core current sensor as shown in Figure 3
below. Lifting up on the latch with a flat-tip screwdriver as shown in Figure 4 below can also open the unit. Press down firmly on
the cover to close the current sensor. An audible "click" will be heard as the tab slides over the tongue on the base.
Caution: Mating surfaces of the magnetic core are exposed when the sensor is open. Silicone grease, present on the cores to
!
prevent rust, may capture grit and dirt if care is not exercised. Operation can be impaired if anything prevents good
contact between pole pieces. Visually check the mating parts of the core before closing the current sensor.
Please Read Instructions Carefully Before Installation!
3X
Figure 1: Sensor Placed on Rail
Figure 3: Opening Sensor by Hand
2305 Pleasant View Rd.  Middleton Industrial Park  Middleton, WI 53562
PH: (608) 831-2585  FAX (608) 831-7407
File Name: I0000142 Rev 6 Doc.
Installation and Operation Instructions
3X
Figure 2: Sensor Removed from Rail
Figure 4: Opening w/ Screwdriver
Page 1 of 3
Part # A/SCTE-50, A/SCTE-250,
A/SCTV-50, A/SCTV-250

Advertisement

loading
Need help?

Need help?

Do you have a question about the A/SCTE-50 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for aci A/SCTE-50

  • Page 1 Installation and Operation Instructions Part # A/SCTE-50, A/SCTE-250, A/SCTV-50, A/SCTV-250 Automation Components, Inc. Please Read Instructions Carefully Before Installation!  Safety  This product is not intended to be used for Life or Safety applications.   This product is not intended for use in any hazardous or classified locations.
  • Page 2  Wiring ACI recommends the use of a 2 conductor 16 to 22 AWG shielded cable, copper wire only for all Analog current sensor installations. A maximum wire length of 30 meters (98.4 feet) should be used between the A/SCTE and A/SCTV Series current sensors and the Building Management System or controller.
  • Page 3  Current Conversion Formulas To convert the current sensor output signal to a current reading. 0-10 Volt output to Current reading (0 Volts = 0 Amps and 10 Volts = 250 Amps for A/SCTV-250 Example: 5 Volts current sensor output signal Total Span = 250 Amps Multiplier = 10V-0V/Total Span = .04 (5 Volts) / 0.04 = 125 Amps...

This manual is also suitable for:

A/scte-250A/sctv-50A/sctv-250