Auxiliary (Electric) Heat Control
The 50HCQ unit can be equipped with one or two auxiliary elec-
tric heaters, to provide a second stage of heating. The DFB will
energize this Heating System for a Stage 2 Heating Command
(heaters operate concurrently with compressor(s) in the Stage 1
Heating cycle), for an Emergency Heating sequence (compressors
are off and only the electric heaters are energized) and also during
the Defrost cycle (to eliminate a "cold blow" condition in the
space).
Defrost
The defrost control mode is a time/temperature sequence. There
are two time components: The continuous run period and the test/
defrost cycle period. The temperature component is provided by
Defrost Thermostat 1 and 2 (DFT1 and DFT2) mounted on the
outdoor coil.
The continuous run period is a fixed time period between the end
of the last defrost cycle (or start of the current Heating cycle)
during which no defrost will be permitted. This period can be set
at 30, 60, 90, or 120 minutes by changing the positions of DIP
switches SW1 and SW2 (see Fig. 35 and Table 4). The default run
period is 30 minutes.
Shorting the jumpers for a period of 5 to 20 seconds bypasses the
remaining continuous run period and places the unit in a Forced
Defrost mode. If the controlling DFT is closed when this mode is
initiated, the unit will complete a normal defrost period that will
terminate when the controlling DFT opens or the 10 minute
defrost cycle limit is reached. If the controlling DFT is open when
this mode is initiated, the Defrost cycle will run for 30 seconds.
Both modes end at the end of the Defrost cycle.
Fig. 35 — DIP Switch Settings - Defrost Board

ELECTRIC HEATERS

50HCQ units may be equipped with field-installed accessory elec-
tric heaters. The heaters are modular in design, with heater frames
holding open coil resistance wires strung through ceramic insula-
tors, line-break limit switches and a control contactor. One or two
heater modules may be used in a unit.
Heater modules are installed in the compartment below the indoor
(supply) fan outlet. Access is through the indoor access panel.
Heater modules slide into the compartment on tracks along the
bottom of the heater opening. See Fig. 36-38.
Not all available heater modules may be used in every unit. Use
only those heater modules that are UL listed for use in a specific
size unit. Refer to the label on the unit cabinet for the list of ap-
proved heaters.
Unit heaters are marked with Heater Model Numbers, but heaters
are ordered as and shipped in cartons marked with a correspond-
ing heater Sales Package part number.
NOTE: The value in position 9 of the part number differs between
the sales package part number (value is 1) and a bare heater model
number (value is 0).
Table 4 — DIP Switch Positions
1
2
1
0
60 minutes
1
2
1
1
0
0
90 minutes
DISCONNECT MOUNTING
LOCATION
UNIT BLOCK-OFF
PANEL
Fig. 36 — Typical Access Panel Location (3-6 Ton)
DISCONNECT
EMT OR RIGID CONDUIT
MOUNTING
(FIELD-SUPPLIED)
LOCATION
MAIN
BRACKET AND
CONTROL
CONDUIT
BOX
DRIP BOOT
Fig. 37 — Typical Component Location
Fig. 38 — Typical Module Installation
21
1
2
1
0
120 minutes
Fan Delay
OUTDOOR
ACCESS PANEL
SINGLE
CENTER
POINT BOX
POST
SINGLE POINT
BOX
HEATER
HEATER
MOUNTING
MODULE
MODULE
SCREW
(LOCATION 1)
(LOCATION 2)
CONTROL WIRE TERMINAL BLOCK
3
On
Off
INDOOR
ACCESS
PANEL
MANUAL RESET
LIMIT SWITCH
HEATER
COVERS
HEATER
MOUNTING
BRACKET
TRACK
FLANGE

Advertisement

Table of Contents
loading

This manual is also suitable for:

Weathermaster 50hcq 05 seriesWeathermaster 50hcq 06 series50hcqa0450hcqa0550hcqa06Weathermaster 50hcq 04 ... Show all

Table of Contents