Honeywell VR4304 Series Manual page 4

Intermittent pilot combination gas control

Advertisement

5. Remove seals over gas control inlet and outlet if
necessary.
6. Connect pipe to gas control inlet and outlet. Use
wrench on the square ends of the gas control. If a flange is
used, place wrench on flange rather than on gas control.
Refer to Figs. 4 and 5.
Connect Pilot Gas Tubing
1. Cut tubing to desired length and bend as necessary
for routing to pilot burner. Do not make sharp bends or
deform the tubing. Do not bend tubing at gas control or
pilot burner after compression fitting has been tightened
because this can result in gas leakage at the connection.
2. Square off and remove burrs from end of tubing.
3. Unscrew compression fitting from the pilot outlet.
See Fig. 4. Slip the fitting over the tubing and slide out of
the way.
Fig. 5—Proper use of wrench on gas control with and without flanges.
APPLY WRENCH
FROM TOP OR
BOTTOM OF GAS
CONTROL TO
EITHER SHADED AREA
NOTE: When replacing a gas control, cut off old compres-
sion fitting and replace with the new compression fitting
provided on the gas control. Never use the old compres-
sion fitting because it may not provide a gas-tight seal.
4. Push tubing into the pilot gas tapping on the outlet
end of the control until it bottoms. While holding tubing all
the way in, slide compression fitting into place, engage
threads and turn until finger tight. Then tighten one more
turn with wrench. Do not overtighten. Refer to Fig. 6.
5. Connect other end of tubing to pilot burner according
to pilot burner manufacturer instructions.
WIRING
Follow the wiring instructions furnished by the appli-
ance manufacturer, if available, or use the following general
instructions. Where these instructions differ from the appli-
ance manufacturer, follow the appliance manufacturer
instructions.
69-0695—2
WHEN FLANGE IS NOT USED
Fig. 4—Top view of gas control.
PRESSURE REGULATOR
ADJUSTMENT (UNDER
CAP SCREW)
INLET
PRESSURE TAP
INLET
GAS CONTROL KNOB
M3043A
Fig. 6—Always use new compression fitting.
All wiring including insulated quick connect terminals
must comply with applicable electrical codes and ordinances.
Disconnect power supply before making wiring connec-
tions to prevent electrical shock or equipment damage.
1. Check the power supply rating on the gas control and
make sure it matches the available supply. Install thermo-
stat and other controls as required.
4
CONVENIENCE
WIRING
TERMINALS (2)
TERMINALS (2)
(OPTIONAL)
PILOT OUTLET
PILOT ADJUSTMENT
(UNDER CAP SCREW)
WHEN FLANGE IS USED
APPLY WRENCH
TO FLANGE ONLY
M9151
GAS CONTROL BODY
TIGHTEN NUT ONE TURN
BEYOND FINGER TIGHT
FITTING BREAKS OFF AND CLINCHES
TUBING AS NUT IS TIGHTENED
OUTLET
PRESSURE
TAP
OUTLET
TO
BURNER
M3076A