12 Inspection and maintenance
12.1
Complete Service Interval Record section
After servicing, complete the relevant Service Interval
Record section of the Benchmark Checklist located on
the inside back pages of this document.
12.2
Using original seals
If you replace components, use only the enclosed original
seals; additional sealing materials are not required.
12.3
Observing inspection and maintenance
intervals
Adhere to the minimum inspection and maintenance in-
tervals. The inspection may require maintenance to be
carried out earlier, depending on the results.
Inspection and maintenance work (→ Appendix)
12.4
Checking the CO₂ content
1.
Start up the product with check programme (P.01).
Overview of the check programmes (→ Page 27)
2.
Wait until the value that is read is stable.
Waiting period for reading a stable value: 5 min
1
3.
Unscrew the cover from the flue gas analysis point (1).
4.
Measure the CO₂ content at the flue gas analysis point
(1).
5.
Compare the measured value with the corresponding
value in the table.
Checking the CO₂
content
CO₂ at full load
CO at full load
CO/CO₂
The value is OK.
The value is not OK; you cannot start up the
product.
Set the CO₂ content. (→ Page 33)
0020230535_07 ecoFIT pure Installation and maintenance instructions
Removed
Fitted front
front casing
casing
Natural gas H
Natural gas H
9.0 ±1.0 vol. %
9.2 ±1.0 vol. %
≤ 250 ppm
≤ 250 ppm
≤ 0.0031
≤ 0.0031
12.5
Setting the CO₂ content
Condition: CO₂ content needs adjustment
Remove the sticker.
Turn the screw (1) to set the CO₂ content (value with
front casing removed).
To increase the CO₂ content: Turn anti-clockwise
To decrease the CO₂ content: Turn clockwise
Only carry out the adjustment in increments of 1/8 turn
and wait approximately 1 minute after each adjustment
until the value has stabilised.
Compare the measured value with the corresponding
value in the table.
Setting the CO₂ con-
tent
CO₂ at full load
Set for Wobbe index
W₀
O₂ at full load
CO at full load
CO/CO₂
If the setting is not in the specified adjustment range,
you must not start up the product.
Inform Customer Service.
Check whether the air-quality requirements with regard
to carbon monoxide are fulfilled.
Install the front panel.
12.6
Removing the gas-air mixture unit
Note
The gas-air mixture unit consists of three main
components:
– Fan
– Gas valve assembly
– Burner hood
1.
Switch off the product via the main switch.
2.
Close the gas stopcock.
3.
Remove the front casing. (→ Page 18)
A
B
Removed
Fitted front
front casing
casing
Natural gas H
Natural gas H
9.0 ±0.2 vol. %
9.2 ±0.2 vol. %
14.09 kW⋅h/m³
14.09 kW⋅h/m³
4.5 ±1.8 vol. %
≤ 250 ppm
≤ 250 ppm
≤ 0.0028
≤ 0.0028
1
33