1.0 Safety Information
IMPORTANT: Installation or replacement of units or spare parts must be carried out by a qualified
or Nuaire approved service engineer/ electrician and in accordance with IEE or local national wiring
regulations.
2.0 Introduction
The Nuaire XS Ceiling Fan Kit is available in 6, 9 and 12 inch impeller
sizes suitable for supply or extract and can be the heart of a room's
automatic ventilation system.
Ensure adequate air replacement for the fan and any fuel burning
appliance in the room.
Figure 1. Main components of ceiling installation assembly.
Mounting
Brackets
Duct Adaptor
Mounting
Screws
2.1 Switching
Operated via a separately wired 3 amp fused spur (by others) or
operated via the optional XS-MFC remote controller allowing supply or
extract, variable speed and automatic or manual switching of several
fans if desired.
3.0 Dimensions
Figure 2.
nuaire.co.uk
029 2085 8400
XS Ceiling Fan Kits 50 / 60Hz
Supply / Extract Units
Installation and Maintenance
Internal Grille
Fan assembly
Front view
XS6CL (6 inch)
Rear view
Required ceiling/panel aperture
270 x 270mm sq.
Cable entry
Side view
Duct Adaptor Outlet dia.*
6 inch unit 200mm dia.
9 inch unit 250mm dia.
12 inch unit 350mm dia.
2.2 Sensors
Sensors are available as remote units or integral 'plug in' units. They
are able to control multiple fans, depending on sensor and fan types.
Integral sensors are quick and easy to install and are aesthetically
pleasing, whilst remote sensors give the benefit of location close to
the pollutant source. Remote sensors can be fitted with an optional
security strap to prevent unwanted tampering.
2.3 General
The removable interior grille provides easy access while the external
rotor motor makes for simple removal of the push-on impeller for
cleaning. Upward angled interior grille vanes shield workings from view.
The fan is IP24 splash proof approved with the motor rated at IP44.
Fan casing, impeller and shutter shall be manufactured from UV
stabilised ABS polymer. All models shall include an economy /high
efficiency setting facility and are dove grey in colour.
2.3.1 Coding For Ceiling Fan Kits
Description
6 inch Ceiling Fan Kit Complete
9 inch Ceiling Fan Kit Complete
12 inch Ceiling Fan Kit Complete
* H indicates 220V 60Hz 1ph
Ceiling Fan Kits are supplied as a complete package with all
installation parts included.
XS9CL (9 inch)
272mm
269mm
342mm
Required ceiling/panel aperture
340 x 340mm sq.
Cable entry
137 mm*
*To centre of
'duct'
134 mm*
269 mm
337 mm
200 mm*
200 mm*
128mm
*Duct Adaptor
130mm
15. 09. 17. Leaflet Number 671052
Code (50 Hz)
Code* (60 Hz)
XS6CL
XS9CL
XS12CL
XS12CL (12 inch)
342mm
420mm
Required ceiling/panel aperture
430 x 430mm sq.
Cable entry
175mm*
*To centre of
'duct'
206 mm*
171 mm*
413mm
230 mm*
200 mm*
250 mm*
169 mm
The EMC Directive
2014/30/EU
The Low Voltage
Directive
2014/35/EU
XS6CLH
XS9CLH
XS12CLH
420mm
214 mm*
*To centre of
'duct'
350 mm*
1

Advertisement

Table of Contents
loading

Summary of Contents for NuAire XS Series

  • Page 1 2014/35/EU 1.0 Safety Information IMPORTANT: Installation or replacement of units or spare parts must be carried out by a qualified or Nuaire approved service engineer/ electrician and in accordance with IEE or local national wiring regulations. 2.0 Introduction 2.2 Sensors Sensors are available as remote units or integral ‘plug in’...
  • Page 2: Installation

    Fix the metal brackets to the cross battens. Offer the fan up into the duct Feed the supply cable through the duct adaptor. adaptor and fix using the two screws. nuaire.co.uk 029 2085 8400 15. 09. 17. Leaflet Number 671052...
  • Page 3 There will be a short delay on start-up and shutdown of approximately 40 seconds, this is normal. Fix the electrical connection before offering up the internal grille. Note grille clips over top edge before being fixed. nuaire.co.uk 029 2085 8400 15. 09. 17. Leaflet Number 671052...
  • Page 4: Electrical Installation

    Connect link wire between L2 & L4 for extract OR connect link wire between L2 & L3 for supply. Connect switched live signal to L5 for integral timer module. nuaire.co.uk 029 2085 8400 15. 09. 17. Leaflet Number 671052...
  • Page 5: Electrical Specification

    Up to 5 fans (size 6"/9") can be controlled by one XS-MFC. Up to 2 fans (size 12") can be controlled by one XS-MFC. Do not mix different fan sizes on the same controller. nuaire.co.uk 029 2085 8400 15. 09. 17. Leaflet Number 671052...
  • Page 6 Plug the connector into the required sensor module. Screw the sensor module into position. Push out the sensor area cover from the grille. Push the repacement cover into the grille front. nuaire.co.uk 029 2085 8400 15. 09. 17. Leaflet Number 671052...
  • Page 7 Feed approx. 200mm of supply cable into the box Connect the end of the cable into the control block. Fit the control into the backplate box and secure. Test the installation. nuaire.co.uk 029 2085 8400 15. 09. 17. Leaflet Number 671052...
  • Page 8: Maintenance

    Telephone 02920 858 400 8.0 Replacement Of Parts aftersales@nuaire.co.uk As a manufacturer Nuaire is aware that time is important. In the event of a breakdown of this equipment, it should be adequately packaged and returned to Nuaire. Please telephone Nuaire before posting your unit. A returns number will be issued to identify your package.

This manual is also suitable for:

Xs6clXs9clXs12clXs6clhXs9clhXs12clh

Table of Contents