Electrical Specification - NuAire XS Series Installation And Maintenance Manual

Table of Contents

Advertisement

Installation and Maintenance
5.1.4 Supply / Extract Fan Operated via remote XS-MFC Control
Double
Fuse
pole
max.
isolator
3 amp
L
L1
N
N
mains
supply
XS-MFC controller
Remote switch may be set: On/Off, Forward/Reverse, Economy/Std.
(variable speed), Auto/Manual.
5.1.5 Supply / Extract Fan Operated via remote XS-MFC Control
and Remote Sensor
Double
Fuse
pole
max.
isolator
3 amp
L
L1
N
N
mains
supply
XS-MFC controller
Remote switch may be set: On/Off, Forward/Reverse, Economy/Std.
(variable speed), Auto/Manual.
One or more Remote Sensors may be wired in parallel to one XS-MFC
Control.
Humidity Sensor: XS-HR
Air Quality Sensor: XS-AQR
Passive Infra-Red Sensor: XS-PIRR
5.1.6 Supply / Extract Fan Operated via remote XS-MFC Control
and an Integral Sensor
Double
Fuse
pole
max.
isolator
3 amp
L
L1
N
N
mains
supply
XS-MFC controller
Remote switch may be set: On/Off, Forward/Reverse, Economy/Std.
(variable speed), Auto/Manual.
Maximum one Integral Sensor per fan, 6/9/12 denotes unit size identity.
Humidity Sensor: XS-H6/9/12
Air Quality Sensor: XS-AQ6/9/12
Passive Infra Red Sensor: XS-PIR6/9/12
Temperature Sensor: XS-TH6/9/12
Run on Timer: XS-TA6/9/12.
A single sensor will switch all fans if more than one fan is being
operated by a single XS-MFC controller.
NOTE: Multi-fan options:
Up to 5 fans (size 6"/9") can be controlled by one XS-MFC.
Up to 2 fans (size 12") can be controlled by one XS-MFC.
Do not mix different fan sizes on the same controller.
nuaire.co.uk
029 2085 8400
L4
L3
L2
L1
N
XS Fan unit
Remote sensor
L2 L1 N
L4
L3
L2
L1
N
XS Fan unit
Required if using
integral Timer
L5
L4
L4
L3
L3
L2
L2
L1
L1
N
N
XS Fan unit with
integral sensor
5.2 Unit Consumption & Weight
L5
L4
Model
L3
L2
XS6CL supply & extract
L1
N
XS9CL supply & extract
XS12CL supply & extract
Note figures are for extract only at 50hz.

5.3 Electrical Specification

230V ~ 50Hz / 220V ~ 60Hz Class I. Motor thermally protected by
overload device. Cable: 1mm max. or min. Fuse: 3 amp (if fan is supplied
from a 5A lighting circuit, no local fuse is required).
Note: If 2 x 12 inch fans or 3 x 6 or 9 inch fans are used in the same
operating mode in the same room they should all be controlled from
L5
the same MFC speed control. This avoids the possibility of one fan (if
L4
speed controlled at a lower flow rate) being stalled by the other fan(s).
L3
Adequate make-up air provision sufficient to provide ventilation in
L2
accordance with building regulations is required in all rooms. This
L1
should be checked during commissioning with all fans in the same room
N
running together in all possible configurations.
The automatic shutters, motor bearings should be frequently inspected
and maintained to ensure they open fully/operate satisfactorily. Use
of an RCD and fused spur with 1A, Bussmann TDC180, BS1362, fuse
(Farnell order no: 1123029) for 1 fan or 2A, Bussmann TDC180, BS1362
fuse (Farnell order no: 1123032) for 2 or 3 fans is recommended.
Always confirm airflow direction before commissioning.
15. 09. 17. Leaflet Number 671052
XS Ceiling Fan Kits 50/60Hz
Input Power
(W)
Max.
Economy
38
20
50
37
100
70
Weight
(kg)
3.95
5.5
8.7
5