Si00-978
Step
4
Disconnect the
connector for the fan
motor [S70] and release
the 4 clamps attached
to the electrical box.
Release the fan motor
5
lead wire.
Disconnect the
6
connectors at the front.
Removal Procedure
Procedure
[S70]
Fan motor lead wire
[S20]
[S90]
When reassembling, insert
Ferrite core
each clamp into the small
hole.
For the ferrite
core of fan
motor
For the thermistor
ASSY harnesses
(either hole)
(R17234)
: When reassembling, do not
use these 2 hooks.
(R18636)
[S20]: electronic expansion
[S80]
[S80]: four way valve coil
[S90]: thermistors
(R9622)
Removal of Electrical Box
Points
For the ferrite core
of electronic
expansion valve coil
For the four way
valve coil harness
(R16919)
valve coil
21