Outdoor Unit - Samsung AC026RN1DKG Service Manual

System air conditioner
Hide thumbs Also See for AC026RN1DKG:
Table of Contents

Advertisement

Troubleshooting

4-2-4 Outdoor Unit

No. Error Code
1
E108
Error due to duplicated communication address Check on repeated indoor unit main address
Error on room temperature sensor of indoor unit
2
E121
(Short or Open)
3
E122
Error on EVA IN sensor of indoor unit (Short or Open) Indoor unit EVA_IN Thermistor Open/Short
4
E123
Error on EVA OUT sensor of indoor unit (Short or Open) Indoor unit EVA_OUT Thermistor Open/Short
5
E153
Error on float switch (2nd detection)
6
E154
Indoor fan error
Error due to connecting outdoor units that do
7
E164
not support the Wind-Free function
Communication error between the indoor unit
and outdoor unit (Pre-tracking failure or when
the actual number of indoor units are different
8
E201
from the indoor unit quantity setting on the
outdoor unit) Error due to communication
tracking failure after initial power is supplied (The
error occurs regardless of the number of units.)
Communication error between indoor unit and
9
E202
outdoor unit (When there is no response from
indoor units after tracking is completed)
Communication error between the outdoor unit
and main micom (For PF #4 to #6 controllers,
10
E203
error will be determined from the time when
the compressor is turned on.)
Error on outdoor temperature sensor (Short or
11
E221
Open)
12
E231
Error on outdoor COND OUT sensor (Short or Open) Check Cond-Out sensor Open / Short
Error on discharge temperature sensor of
13
E251
compressor 1 (Short or Open)
14
E320
Error on OLP sensor (Short or Open)
15
E403
Compressor down due to freeze protection control Check Outdoor Cond.
16
E404
System stop due to overload protection control Check Comp. when it starts
High Pressure Switch Error or High Pressure
17
E407
Switch Connector Open
18
E416
System stop due to discharge temperature
19
E422
Blockage detected on high pressure pipe
4-16
Meaning
Remarks
Indoor unit Room Thermistor Open/Short
Indoor unit Float Switch Open/Short Drain
Pump operation Check
Check on indoor unit indoor Fan operation
Check outdoor main PBA S/W, Check
outdoor EEPROM data
Check indoor quantity setting in outdoor
Check electrical connection and setting
between indoor unit and outdoor unit
Check electrical connection and setting
between
outdoor unit MAIN PBA - INVERTER PBA
Check Outdoor sensor Open / Short
Check Discharge sensor Open / Short
Check OLP sensor Open / Short
Check Comp Pressure or Check the Connection
of the CN003 on the MAIN-OUT PBA
(Error that only covers an outdoor unit capacity
of 7.1 KW or less)
-
1. Check if the service valve is open
2. Check for refrigerant leakage (pipe
connections, heat exchanger) and charge
refrigerant if necessary
3. Check if there's any blockage on the
refrigerant cycle (indoor unit/outdoor unit)
4. Check if Additional refrigerant has been
added after pipe extension