Configuration
The TEC-EYE hand-held diagnostic tool (see Figure
19) is needed to set up the th-TUNE. For additional
information about using the TEC-EYE, see the latest
revision of MULTI-TEC Service Instructions manual
2100-665.
1. Connect the TEC-EYE diagnostic tool to the control
board located in the wall-mount unit. The TEC-EYE
connects to the control board via an RJ11 modular
phone connector.
The initial screen that will display on the TEC-EYE
is the status screen for the MULTI-TEC wall unit.
If the th-TUNE has been properly connected to the
wall-mount unit, the status screen should look like
Figure 18.
FIGURE 18
MULTI-TEC Status Screen
TEC-EYE (Bard P/N 8301-059) Display and Interface (Status Screen Shown)
ALARM KEY
MENU KEY
ESCAPE KEY
ALARM KEY
Allows viewing of active alarms
Silences audible alarms
Resets active alarms
MENU KEY
Allows entry to Main Menu
ESCAPE KEY
Returns to previous menu level
Cancels a changed entry
2. Press MENU key to access the Main Menu screen.
3. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
4. Press UP or DOWN keys to scroll to Adv Sys Config;
press ENTER key.
5. Press UP or DOWN keys to scroll to th_Tune Setup
B4 screen.
6. Press ENTER key to scroll to Enable parameter
(see Figure 19).
7. Press UP or DOWN key to change the value from
NO to YES.
If the th-TUNE is wired correctly, it will display the
temperaure, humidity and setpoints from the wall-
mount unit controller. If the th-TUNE is not wired
correctly, it will display "Cn".
th-TUNE Configuration
FIGURE 20
UP KEY
Steps to next screen in the display menu
Changes (increases) the value of a modifiable field
ENTER KEY
Accepts current value of a modifiable field
Advances cursor
DOWN KEY
Steps back to previous screen in the display menu
Changes (decreases) the value of a modifiable field
FIGURE 19
UP KEY
ENTER KEY
DOWN KEY
Manual
2100-678C