29. Tank re-heat temp.
Set temp to perform reboil of tank water.
(When boiled by heat pump only, (51°C – Tank re-heat temp) shall become
max temp.)
Setting range is -12°C ~ -2°C
30. Sterilization
Initial setting: 65°C 10min
Set timer to perform sterilization.
1 Set operating day & time. (Weekly timer format)
2 Sterilization temp (55~75°C
3 Operation time (Time to run sterilization when it reached setting temp
5min ~ 60min)
User shall set whether to use or not to use sterilization mode.
11.3.5 Service Setup
31. Pump maximum speed
Normally setting is not necessary.
Please adjust when need to reduce the pump sound etc.
Besides that, it has Air Purge function.
32. Pump down
Operate pump down operation
33. Dry concrete
Operate concrete curing operation.
Select Edit, set temp for every stage (1~99 1 is for 1 day).
Setting range is 25~55°C
When it is turned ON, dry concrete starts.
When it is 2 zone, it dries both zones.
34. Service contact
Able to set name & tel no. of contact
person when there is breakdown
etc. or client has trouble. (2 items)
Initial setting: -8°C
If use back-up heater, it is 65°C)
Initial setting: Depend on model
Service setup
Pump down:
ON
Confirm
Service setup
Service contact:
Contact 1
Contact 2
Select
①  ③
Service setup
Flow rate
88:8 L/min
Select
17:26, Wed
Service setup
Pump down:
45°C
40°C
35°C
30°C
1
2
3
4
17:26, Wed
Contact-1: Bryan Adams
ABC/ abc
A B C D E F G H I J K L M N O P Q R
S T U V W X Y Z
j k l m n o p q r s t u v w x y z
Confirm
Select
77
-12°C ~ -2°C
17:26, Wed
Max. Duty
Operation
Air Purge
0xCE
17:26, Wed
Pump down operation
in progress!
ON
OFF
Confirm
40°C
35°C
5
6
Stage
0-9/ Other
a b c d e f g h i
Enter

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-sdc05h3e5Wh-ud03he5Wh-ud05he5

Table of Contents