16.5.41 Power Factor Correction (PFC) Abnormality (F41)
Malfunction Decision Conditions:
During operation of cooling and heating, when the PFC protection circuitry in the outdoor unit PCB (main) senses
abnormal high DC voltage level.
Malfunction Caused:
1
Power supply surge.
2
Compressor windings not uniform.
3
Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue 4 times in 10 minutes.