Panasonic WH-SDC03H3E5 Service Manual page 62

Air-to-water heatpump
Hide thumbs Also See for WH-SDC03H3E5:
Table of Contents

Advertisement

11.2.3 How To Fix Cable
11.2.3.1
Connecting with external
device (optional)
All connections shall follow to the local national
wiring standard.
It is strongly recommended to use manufacturer-
recommended parts and accessories for
installation.
For connection to main PCB.
1. Two-way valve shall be spring and electronic type,
refer to "Field Supply Accessories" table for details.
Valve cable shall be (3 × min 1.5 mm
designation 60245 IEC 57 or heavier, or similarly
double insulation sheathed cable.
* note: - Two-way Valve shall be CE marking
compliance component.
- Maximum load for the valve is 9.8VA.
2. Three-way valve shall be spring and electronic
type. Valve cable shall be (3 × min 1.5 mm
type designation 60245 IEC 57 or heavier, or
similarly double insulation sheathed cable.
* note: - Shall be CE marking compliance
component.
- It shall be directed to heating mode when
it is OFF.
- Maximum load for the valve is 9.8VA.
3. Room thermostat cable must be (4 or 3 × min 0.5
2
mm
), of type designation 60245 IEC 57 or
heavier cord, or similarly double insulation
sheathed cable.
4. Maximum output power of booster heater shall be
≤ 3 kW. Booster heater cable must be (3 × min 1.5
mm
2
), of type designation 60245 IEC 57 or
heavier.
5. Extra pump cable shall be (2 × min 1.5 mm
type designation 60245 IEC 57 or heavier.
6. Boiler contact cable shall be (2 × min 0.5 mm
type designation 60245 IEC 57 or heavier.
7. External control shall be connected to 1-pole
switch with min 3.0 mm contact gap. Its cable
must be (2 × min 0.5 mm
of PVC-sheathed or rubber-sheathed cable.
* note: - Switch used shall be CE compliance
component.
- Maximum operating current shall be less
than 3A
.
rms
8. Tank sensor shall be resistance type, please refer
to Graph 7.1 for the characteristic and details of
sensor. Its cable shall be (2 × min 0.3 mm
double insulation layer (with insulation strength of
min 30V) of PVC-sheathed or rubber-sheathed
cable.
2
), of type
2
), of
2
), of
2
), of
2
), double insulation layer
2
),
Tank Sensor Resistant Vs Temperature
16000
14000
12000
10000
8000
6000
4000
2000
0
Graph 7.1: Tank sensor characteristic
9. Room sensor zone 1 cable shall be (2 × min 0.3
2
mm
) double insulation layer of PVC-sheathed or
rubber-sheathed.
10. Outdoor air sensor cable shall be (2 × min 0.3
2
mm
) double insulation layer of PVC-sheathed or
rubber-sheathed.
11. Tank OLP cable must be (2 × min 0.5 mm
double insulation layer of PVC-sheathed or
rubber-sheathed cable.
Main PCB
Power Supply 2
RCCB/ELCB
Power Supply 1
RCCB/ELCB
Indoor
terminal for
connecting
cables
Holder (Clamper)
How to guide the optional cables and power supply cord
(view without internal wiring)
Optional cables:
3-way valve
cable
2-way valve cable
Room thermostat zone
1 cable
Booster heater cable
Extra pump cable
Boiler contact cable
For connection to optional PCB
1. By connecting optional PCB, 2 Zone temperature
control can be achieved. Please connect mixing
62
-30 -20 -10
0
10
20
˚C
Optional cables:
External control
cable
Tank sensor cable
Room sensor
zone 1
Outdoor air sensor
cable
Tank OLP cable
Remote controller
cable
Power Supply 1 cord
Power Supply 2 cord
Indoor Unit/Outdoor Unit Connecting cable
30
2
),
Bind optional
cables with
these bands
Bind optional
cables with
these bands