16.5.10 Compressor Low Pressure Protection (H42)
Malfunction Decision Conditions:
During operation of heating and after 5 minutes compressor ON, when outdoor pipe temperature below -29°C or
above 26°C is detected by the outdoor pipe temperature sensor.
Malfunction Caused:
1
Dust accumulation on the outdoor unit heat exchanger.
2
Air short circuit at outdoor unit.
3
2 way valve partially closed.
4
Faulty outdoor unit fan motor.
5
Refrigerant shortage (refrigerant leakage).
6
Clogged expansion valve or strainer.
7
Faulty outdoor pipe temperature sensor.
8
Faulty outdoor unit main PCB (main).