16.4

Error Codes Table

Diagnosis display
Abnormality/Protection control
H00
No abnormality detected
H12
Indoor/Outdoor capacity unmatched
Outdoor compressor temperature sensor
H15
abnormality
Indoor refrigerant liquid temperature
H23
sensor abnormality
H28
Abnormal solar sensor
H31
Abnormal swimming pool sensor
H36
Abnormal buffer tank sensor
H38
Brand code not match
H42
Compressor low pressure abnormality
H43
Abnormal Zone 1 sensor
H44
Abnormal Zone 2 sensor
H62
Water flow switch abnormality
H63
Abnormal low pressure sensor
H64
Refrigerant high pressure abnormality
H65
Abnormal deice water circulation
H67
Abnormal External Thermistor 1
H68
Abnormal External Thermistor 2
H70
Back-up heater OLP abnormality
H72
Tank sensor abnormal
H74
PCB communication error
H75
Low water temperature control
Indoor - control panel communication
H76
abnormality
H90
Indoor/outdoor abnormal communication
H91
Tank heater OLP abnormality
H95
Indoor/Outdoor wrong connection
Outdoor high pressure overload
H98
protection
H99
Indoor heat exchanger freeze prevention
F12
Pressure switch activate
F14
Outdoor compressor abnormal revolution
F15
Outdoor fan motor lock abnormality
F16
Total running current protection
Outdoor compressor overheating
F20
protection
Abnormality judgement
90s after power supply
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
When indoor and outdoor
brand code not same
Continue for 5 sec.
Continue for 5 sec.
Continue for 1 min.
4 times in 20 minutes
Continue for 5 sec.
water flow > 7 l/min continously
for 20 second during anti
freeze deice
Continue for 5 sec.
Continue for 5 sec.
Continue for 60 sec.
Continue for 5 sec.
Communication or transfer
error
Room heater disable and deice
request to operate under low
water temperature
> 1 min after starting operation
Continue for 60 sec.
4 times occurrence within 20
minutes
4 times occurrence within 20
minutes
2 times occurrence within 30
minutes
3 times occurrence within 20
minutes
4 times occurrence within 30
minutes
144
Primary location to verify
 Indoor/outdoor connection wire
 Indoor/outdoor PCB
 Specification and combination table in
catalogue
 Compressor temperature sensor
(defective or disconnected)
 Refrigerant liquid temperature sensor
(defective or disconnected)
 Solar temperature sensor (defective or
disconnected)
 Pool temperature sensor (defective or
disconnected)
 Buffer tank sensor (defective or
disconnected)
 Outdoor pipe temperature sensor
 Clogged expansion valve or strainer
 Insufficient refrigerant
 Outdoor PCB
 Compressor
 Water temperature Zone 1 sensor
 Water temperature Zone 2 sensor
 Water flow switch
 Low pressure sensor (defective or
disconnect)
 Outdoor high pressure sensor
(defective or disconnected)
 Water pump
 Room temperature Zone 1 sensor
 Room temperature Zone 2 sensor
 Back-up heater OLP
(Disconnection or activated)
 Tank sensor
 Indoor main PCB and Sub PCB
 Heater operation must enable to
increase water temperature
 Indoor - control panel
(defective or disconnected)
 Internal/external cable connections
 Indoor/Outdoor PCB
 Tank heater OLP
(Disconnection or activated)
 Indoor/Outdoor supply voltage
 Outdoor high pressure sensor
 Water pump or water leakage
 Clogged expansion valve or strainer
 Excess refrigerant
 Outdoor PCB
 Indoor heat exchanger
 Refrigerant shortage
 Pressure switch
 Outdoor compressor
 Outdoor PCB
 Outdoor fan motor
 Excess refrigerant
 Outdoor PCB
 Compressor tank temperature sensor
 Clogged expansion valve or strainer
 Insufficient refrigerant
 Outdoor PCB
 Compressor