Viessmann Vitodens 200-W B2HA 88 Technical Data Manual page 5

Gas-fired wall-mounted condensing boiler
Hide thumbs Also See for Vitodens 200-W B2HA 88:
Table of Contents

Advertisement

Vitodens 200-W B2HA 88-150, 311- 530 Technical Data
Technical Data
(continued)
Boiler Model No. B2HA
Dimensions
Overall depth
Overall width
Overall height *8
Flue gas *4
Temperature (at boiler return
temperature of 86ºF (30ºC)
- at rated full load
- at rated partial load
Temperature (at boiler return
temperature of 140ºF (60ºC)
Flue gas parameters
Mass flow rate
Natural gas
- at rated heating output
(DHW heating)
- at partial load
Liquid propane gas
- at rated heating output
(DHW heating)
- at partial load
Max. condensate flow rate *5
for NG and LPG
T
/T
=104/86ºF (40/30ºC)
S
R
Condensate connection *6
Boiler flue gas connection *7
Combustion air supply connection
(coaxial)
Sound Rating
- at maximum input
- at minimum input
NOx @ 3% O
2
*A
For high altitude installations 5,000 - 10,000 ft. (1500 m - 3000 m), the input for model B2HA 88, 100, 150,
311, 352, 530 will have an altitude de-ration of 14% for 5,000 ft. (1500 m) and 29% for 10,000 ft. (3000 m)
average of 2.8% / 1,000 ft. (305 m).
*B
The input for model B2HA 112, 399 at 10,000 ft. (3000 m) will have an input de-rate of 13%.
*4
Measured flue gas temperature with a combustion air temperature of 68°F (20°C).
*5
Based on maximum input rate.
*6
Requires 1 inch (25 mm) tubing. See the Installation Instructions of the Vitodens 200-W, B2HA for details.
*7
For side wall vent installations (coaxial system):
Do not exceed max. equivalent length specified in the Installation Instructions of the Vitodens 200-W, B2HA
Venting System.
Side wall co-axial vent installation must include Viessmann protective screen!
For details refer to the Installation Instructions for the Vitodens 200-W, B2HA Venting System.
The Vitodens 200-W can only be common vented with other Vitodens 200-W boilers of the same size and series.
For details refer to the Common Venting Manual.
*8
Add approximately 2b inches (65 mm) for coaxial vent pipe transition adaptor.
*9
Optional low NOx certified by SCAQMD Natural Gas models available.
For information regarding other Viessmann System Technology componentry, please reference the documentation
of each respective product.
88, 311 *A
inches
21
(mm)
(530)
inches
19
mm)
(480)
inches
43b
mm)
(1105)
ºF (ºC)
135 (57)
ºF (ºC)
99 (37)
ºF (ºC)
162 (72)
lb/h (kg/h)
384 (174)
lb/h (kg/h)
115 (52)
lb/h (kg/h)
364 (165)
lb/h (kg/h)
108 (49)
USG/h
3.1
(L/h)
(11.7)
hose nozzle
Ø in.
¾-
1
Ø
in. (mm)
4
/
(110)
3
8
outer
Ø in. (mm)
6 (150)
dB
69
dB
38
100, 352 *A
112, 399 *B
21
27.1
(530)
(689)
19
23
5
(480)
(600)
43b
44b
(1105)
(1128)
135 (57)
124 (51)
99 (37)
102 (39)
162 (72)
158 (70)
384 (174)
463 (210)
115 (52)
116 (53)
364 (165)
509 (231)
108 (49)
130 (59)
3.5
4.35
(13.1)
(16.5)
¾-
¾-
1
4
/
(110)
4
/
(110)
3
3
8
8
6 (150)
6 (150)
69
57
38
40
<20 PPM *9
Technical Data
150, 530 *A
27.1
(689)
/
23
/
5
8
8
(600)
44b
(1128)
140 (60)
102 (39)
165 (74)
558 (253)
116 (53)
613 (278)
130 (59)
5.28
(20.0)
¾-
1
1
4
/
(110)
3
8
6 (150)
61
40
5

Advertisement

Table of Contents
loading

Table of Contents