Viessmann Vitodens 200-W B2HA 88 Technical Data Manual page 37

Gas-fired wall-mounted condensing boiler
Hide thumbs Also See for Vitodens 200-W B2HA 88:
Table of Contents

Advertisement

Vitodens 200-W B2HA 88-150, 311- 530 Technical Data
System Layout 2
Vitodens 200-W, B2HA with one heating circuit and low-loss header
Legend
A
Vitodens 200-W B2HA boiler with
Vitotronic 200, HO1B outdoor reset control
B
Outdoor temperature sensor !
Vitotrol remote (optional)
C
Heating circuit
D
E
Boiler pump
20
DHW circulating pump sA
F
G
DHW storage tank
H
DHW tank temperature sensor %
Expansion tank
I
J
Temperature and pressure relief valve
DHW recirculation pump
K
Low-loss header
L
M
Pressure relief valve
Viessmann temperature sensor for low-loss header ?
N
O
Heating circuit pump
*
Function based on coding of address 53
*
28/20
*
28/20
Installation of ...
radiator heating circuit (high-temp. circuit)
DHW production
... with the following flow conditions:
The flow rate of the heating circuit is greater than the
maximum possible water flow rate of the Vitodens
200-W B2HA boiler (see page 9 for maximum water flow
rate of boiler).
The use of a low-loss header is strongly recommended if
the maximum water flow rate in the application concerned
exceeds the values shown on page 10,
or if the system flow rates are unknown.
The low-loss header is available as accessory part.
IMPORTANT
Please note location of expansion tank.
DHW circulating pump F must pump into the Vitodens
200-W B2HA boiler (as illustrated).
Installation Examples
37