2-16 Dehumidifying Operation

Dehumidifying operation uses the cooling cycle to remove moisture from the air, but by
running an indoor fan at a low speed, to dehumidify without greatly lowering room
temperature. In this mode, the microprocessor automatically controls the ON-OFF
operation between +2 deg. and -2 deg. of the set temperature.
ROOM TEMP.
A range: When the room temperature is in this range, cooling operation starts. However, when
the temperature is below 18°C, the cooling operation does not start.
B range: When the room temperature is in this range, the air conditioner automatically repeats
the dehumidifying cycle of 5 minutes ON, 3 minutes OFF – see Fig. 22 for details.
C range: When the room temperature is in this range, the microprocessor shuts off the air
conditioner.
T+2°C (T+1°C)
SET TEMP. T°C
T–2°C (T–1°C)
COMPRESSOR
OUTDOOR FAN
INDOOR FAN
Body sensor
The indoor fan speed is automatically set to L and cannot be adjusted to M or H.
When the set temperature is either 18 or 19°C, the set temperature is considered the same
as 20°C.
Room temperature is monitored every 8 minutes when it is in the B range to select the best
operation mode.
(DEG)
SET TEMP.
ROOM TEMP
5 MINUTES
3 MINUTES
ON
OFF
ON
OFF
– 41 –
2. Processes and functions
A
+2deg
B
–2deg
C
0448_M_S
ON
ON
L
Fig. 19
AREA
A
B
C
OFF
ON
OFF
ON
0449_M_S
Fig. 20
SM830036
2