2.2.2 Design

Figure 2.2.1 presents the appearance and overall and mounting dimensions of S2000-AR8.

2.2.3 Mounting

The S2000-AR8 is to be installed on walls or within cabinets closely to equipment to be
monitored by the module at places protected against atmospheric precipitations, mechanical damage,
and unauthorized access.
Mounting the module shall be performed in line with requirements of Russian Regulatory
Document РД 78.145-92 "Rules for Performance and Acceptance of Works. Fire and Intrusion Alarm
Installations". The module should be attached at a height suitable for operating and maintenance. If
the S2000-AR8 is housed in unwatched premises it should be at least 2.2 m higher than the floor
level.
The module design provides installing it either on a flat surface using the woodscrews
provided or onto a DIN-rail.
It is acceptable to install the module within mounting enclosures (cabinets, boxes, etc.). If the
module and other units are arranged adjacently then vertical and horizontal distances between them
shall be at least 10 mm each.
The procedure of fastening the S2000-AR8 is described in its Installation Manual available
online on
https://bolid.ru
Figure 2.2.1 Overall and Mounting Dimensions of S2000-AR8
in the section PRODUCTS at the page of S2000-AR8.