1.3
Standard Delivery
Table 1.3.1 represents the content of S2000-AR8 standard delivery.
S2000-AR8 Addressable Eight-Input Module
Accessory Kit:
Resistor C2-33H-0.25-10k ±5%
GOST R ISO 7049 - ST2,9x9,5-St-C-H-A1A Tapping Screw
Woodscrew 1-3x25.016 GOST 1144-80
Wall Plug 6x30
Documentation
S2000-AR8 Addressable Eight-Input Module. Operations Manual
1.4

Arrangement and Operation

1.4.1 S2000-AR8 features eight monitored circuits (or supervised circuits, or device loops) each
providing connection of non-addressable fire and intrusion detectors, control appliances, and
auxiliary devices with dry contact outputs. Both normally closed detectors and normally open
detectors are connectable. The schematic for connecting detectors is shown in Figure 2.2.2.
Triggering of the connected non-addressable detector results in a change in the monitoring circuit
resistance which is detected via the ADC. The relationship between resistance of a monitored circuit
and relevant states and ADC values is represented in Table 3.4.1.
1.4.2 A unique address for communicating data over the polling loop is assigned to each monitored
circuit of the module. Each address is stored in the non-volatile memory of the module and allows
sending messages about conditions at the relevant address point in response to a request of the polling
loop controller.
1.4.3 The module is powered via and communicates data over the polling loop of the polling loop
controller.
1.4.4 The module provides monitoring of the conditions of its enclosure. A message about module
enclosure's entering to the Open state is generated just after the cover has been open. The module
considers its enclosure to be in the Closed state after its cover has been closed for at least 15 s.
1.4.5 S2000-AR8 can be in one of the three operation modes:
– Quiescent Mode: The value of resistance is within the normal range for all the monitored
circuits;
– Alarm Mode: The resistance of at least one monitored circuit has been out of normal range;
– Programming with Address: A Set New Address command has been received from the polling
loop controller over the polling loop, and an activity to confirm setting the address is being
expected (see Section 2.2.5.2).
Item
Table 1.3.1
Quantity
1 pc.
8 pcs.
2 pcs.
3 pcs.
3 pcs.
1 pc.