the  compressor will run at very low frequency. In general, unit will change its running frequency
according toδt to make room temperature closing to set temperature.
(2) Outdoor temperature affects running frequency of the compressor
Outdoor temperature affect compressor's running frequency. Difference inlet temperature of
outdoor unit is adapted by difference compressor running frequency. While outdoor temperature is
about 30℃, the compressor will run in high frequency.
If unit run in "cooling" mode and outdoor temperature is less than -2℃,the controller will shut down
compressor and show error code, while the ambient temperature is over 1℃, the compressor will run
automatically.
(3) Auto fan control in cooling mode
In cooling mode (include cooling in "feel" mode), fan speed is determined by δt, as the following
diagram:
 
RT‐ST
 
 
 
 
 
 
 
 
 
 
 
 
 
4."DRY" Mode Operation
(1) The system for DRY operation used the same refrigerant circle as the cooling one.
(2) When the system operates in DRY mode, at first it operates in cooling mode, the set
temperature (ST) is "RT-2℃". After that, t he system will operate in cooling mode with lowest
fan speed for 30 minutes and then change to middle speed for 30seconds as a cycle. During
the course of this operation, you can't use remote controller to adjust the fan speed but you can
control the vane direction.
(3) In the dry mode, when RT≤12℃, the compressor will stop and operates again at RT≥14℃.
5. "HEATING" Mode Operation (available for Heat Pump only)
(1) Frequency control
Same as the frequency control in cooing mode, the running frequency of compressor is
controlled by controller. Unit change its running frequency according to δt to make the room
temperature closing to the set temperature.
(2) Indoor fan motor control
1) Cold Air Prevention C ontrol
The function is intended to prevent cold air from being discharged when heating mode
selected or while in defrosting.
The indoor fan speed will be controlled as following.
 
 
                   
 
 
 
 
 
In heating operation, if air conditioner turn off, the indoor fan motor will run most for 30
 
δt come down
℃ 
3.5 
High fan
3.0 
Min fan
1.5 
1.0 
Low fan
 
Temperature up
37
33
25
δt come up
Setting
Low fan
34
28
Breeze
Stop
22
Temperature down