4).If the piping is installed to the right, the pipes,
power cable and drain hose must be lagged and
secured onto the rear of the unit with a pipe
connection.
Insert the pipe connection into the relative slot.
Press to join the pipe connection to the base.
10.2.8 Electronic connections
1. Take the cover away.
2. Connect the cable wires to the terminal board
using the same numbering as in the indoor unit.
3. For the electrical connections, see the wiring
diagram on the back of the cover
4. Fasten the cables with a cable-clamp.
5. An efficient earth connection must be ensured.
6. Replace the covers.
10.2.9 Connecting the pipe
Screw the flare nuts to the outdoor unit coupling
with the same tightening procedures described for
the indoor unit.
Note: If the tightening torque is not sufficient, there
will probably be some leakage. With excessive
tightening torque there will also be some leakage,
as the flange could be damaged.
10.2.10 Bleeding
Air and humidity left inside the refrigerant circuit can
cause compressor malfunction. After having
connected the indoor and outdoor units, bleed the
air and humidity from the refrigerant circuit by using
a vacuum pump.
The air and humidity left inside the refrigerant
circulation can cause compressor malfunction.
After having connected the indoor and outdoor
units, bleed the air and humidity from the
refrigerant circulation using a vacuum pump.
Air Conditioner Service Manual
 
 
 
 
 
Outdoor unit
 
service port nut
Wiring diagram on the back of the cover
Screw
Remove the upper cover
connection pipes
flare nuts
liquid tap
gas tap
indoor unit
gas valve
protection caps
s ervice port
Liquid valve
tap
vacuum pump
25 