Wiring the Contact Closure Input (CCI)
The contact closure inputs must be dry contact
closure, solid state, open collector, or active-low
(NPN)/active-high (PNP) output.
• Open collector NPN or active-low on-state voltage
must be less than 2 V and sink 3.0 mA.
• Open collector PNP or active-high on-state voltage
must be greater than 12 V and source 3.0 mA.
• The outputs must stay in the closed or open states
for at least 60 msec in order to be recognized by
the wallstation.
If there is any question as to whether the third-party
device generating these outputs is compatible with
these specifications, contact the manufacturer.
seeTouch
®
(3) 18 AWG
(1.0 mm
2
)
Common
Input 2
Input 1
Signature Series
TM
(3) 18 AWG
2
(1.0 mm
)
Input 1
A
Input 2
B
Common
C
Installation Instructions
Note: If a wallstation has devices connected
to it through contact closure inputs,
CCI1 "presses" the top button and CCI2
"presses" the bottom button. To change
this behavior, refer to Application Note 428
(seeTouch
Advanced Programming Mode)
®
at www.lutron.com.
Exception: On a 2-button wallstation
configured for partitioning, panic, or
sequencing functionality, CCI1 closure
action follows the top button and opening
action follows the bottom button.
seeTouch
International
®
(3) 18 AWG
(1.0 mm
2
)
Common
Input 2
Input 1
Architrave
TM
(3) 18 AWG
2
(1.0 mm
)
Input 1
A
Input 2
B
Common
C
6
Mounting
Carefully mount and align the wallstation as
shown. Screw top and bottom screw into the
control and wallbox. Replace adapter (for insert
versions; screw to control), button assembly, and
faceplate in the order shown.
seeTouch
®
Wallbox
Control
seeTouch
International
®
Wallbox
Control
Wallbox Size
Wallstation Type
(high x wide x deep)
3.7 x 2.2 x 2.75 in
seeTouch
®
95 x 55 x 70 mm
seeTouch
3 x 3 x 1.4 in
®
International
75 x 75 x 35 mm
4.4 x 1.5 x 2.8 in
Signature Series
TM
113 x 39.x 71 mm
4.4 x 1.25 x 2.75 in
Architrave
TM
112 x 32 x 70 mm
Occupant Copy
Occupant Copy
Signature Series
Mounting screws
Adapter
screws
Wallbox
Buttons
Architrave
TM
Adapter
Faceplate
Mounting screws
Adapter screws
Wallbox
Adapter
Buttons
Faceplate
Lutron P/N
241519
Power Up
Turn ON control breaker, or replace main fuse.
241683
Installation is Complete
WBOX-SA1-Q1
For Programming functions, see the
QS Wallstation Programming Guide at
241399
www.lutron.com/qs.
7
TM
Adapter
screws Mounting
screws
Buttons
Control
Adapter
Faceplate
Mounting screws
Control
Faceplate
Installation Instructions