Lutron Electronics QS Wallstation Signature Series Installation Manual page 2

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
QS Wallstation Models
seeTouch
seeTouch
®
®
Keypads
International Keypads
QSWS2-1B
QSWE-2B
QSWS2-2B
QSWE-3B
QSWS2-3B
QSWE-4B
QSWS2-5B
QSWE-5BRL
QSWS2-7B
QSWE-5BRLIR
QSWS2-2BRL
QSWE-6BRL
QSWS2-3BRL
QSWE-7BRL
QSWS2-5BRL
QSWE-8BRL
QSWS2-2BRLIR
QSWE-8BRLIR
QSWS2-3BRLIR
QSWE-10BRL
QSWS2-5BRLIR
QSWS2-1RLD
QSWS2-2RLD
QSWS2-3BD
Signature Series
Architrave
TM
TM
Keypads
Keypads
QSWAS-1B
QSWA-KP5-DN
QSWAS-2B
QSWA-KP5-DW
QSWAS-3B
QSWA-KP7-DN
QSWAS-5B
QSWA-KP7-DW
QSWAS-7B
QSWAS-2BRL
QSWAS-3BRL
QSWAS-5BRL
QSWAS-1RLD
QSWAS-2RLD
QSWAS-3BD
Notes
• Read all instructions carefully before starting
installation.
• Lutron recommends that wallstations be installed
by a qualified electrician.
• Use only a cloth with warm water and mild soap to
clean faceplates (no chemical cleaners).
Installation Instructions
Overview
• QS wallstations can be programmed to control
lights, shades, or lights and shades.
• Unprogrammed (out-of-box) QS wallstations,
Sivoia
QS shades, GRAFIK Eye
QS control
®
®
units, and Energi Savr Node
units will all work
TM
together until they are programmed otherwise.
• Contact closure inputs allow operation with
occupancy/vacancy sensors, partitioning, and
more.
QS Link Limits
• The QS wired communication link is limited to
100 devices and 100 zones. Each QS wallstation
counts as 1 device and 0 zones.
• QS wallstations use 1 power draw unit (PDU) on
the QS link. Refer to the QS Link Power Draw
Units specification submittal (Lutron P/N 369405)
and the diagram on the opposite page for more
information concerning Power Draw Units.
Compatible Components
The following devices are compatible with the QS
link. For more information on each, refer to
www.lutron.com/qs
• GRAFIK Eye
QS control units
®
• QS wallstations
• Sivoia
QS shades
®
• QS Interfaces (contact closure, Ethernet/RS232)
• Quantum
system
®
• Energi Savr Node
units
TM
• QS Sensor Module
• QS Keyswitch
2
Occupant Copy
Power Group Wiring Example
On the QS link, there are devices that supply power and devices that consume power. Each device has a
specific number of Power Draw Units (PDUs) it either supplies or consumes. A Power Group consists of one
device that supplies power and one or more devices that consume power; each Power Group may have
only one power-supplying device. Refer to the QS Link Power Draw Units specification submittal
(Lutron P/N 369405) for more information concerning PDUs.
Within Power Groups on the QS link, connect all 4 terminals (1, 2, 3, and 4), shown by the letter A in the
diagram. Between devices on the QS link that supply power, connect only terminals 1, 3, and 4 (NOT
terminal 2), shown by the letter B on the diagram.
Wiring can be T-tapped or daisy-chained.
A
LUTRON
GRAFIK Eye
QS
®
control unit
B
Control Interfaces
Wallstations
Supplies PDUs
Consume PDUs
Consume PDUs
(Do not connect
Terminal 2: 24 V
)
A
LUTRON
B
Energi Savr Node
TM
unit
Supplies PDUs
(Do not connect
Terminal 2: 24 V
)
A
QS Power Supply
LUTRON
Supplies PDUs
B
(Do not connect
Quantum
Panel
®
Terminal 2: 24 V
)
Supplies PDUs
Occupant Copy
Power Group 1
Connect all 4
A
LUTRON
terminals within a
power group:
1: Common
2: 24 V
Power Group 2
3 and 4: Data
Connect only 3
B
terminals between
LUTRON
LUTRON
power groups:
1: Common
3 and 4: Data
Do not connect
Terminal 2: 24 V
Power Group 3
QS Sensor Module with Occupancy Sensor
Consume PDUs
3
Installation Instructions