Troubleshooting - Bradford White PDV Series Service Manual

Residential & light duty commercial power direct vent models
Hide thumbs Also See for PDV Series:
Table of Contents

Advertisement

Condensing PDV Series
Observe green LED indicator on
electronic gas control. Error flash codes
are displayed with a three second pause
before repeating. Check and repair the
system as noted in the troubleshooting
table below.
LED Status
Control Status
None, control
No electrical
LED not on or
power.
flashing
Stand-by mode,
Short flash once
every four
waiting for call for
seconds
heat (no fault).
Thermostat
"Heartbeat"
calling for heat
alternates
bright/dim
(no fault).
Weak pilot signal
Short flash once
on last call for
per second
heat.
Pressure switch
Two flash, three
not working –
second pause
closed position.
Pressure switch
Three flash,
or blower temp.
three second
switch not
pause
working – open
position.
Excessive tank
Four flash, three
temperature.
second pause
System must be
reset.
Undesired-false
Five flash, three
pilot flame
second pause
present.
Probable Cause
Control power switch in "OFF" position.
Supply voltage interrupted.
Temperature demand is satisfied.
Tank temperature below set point of
thermostat.
1. Unstable pilot.
2. Pilot tube blocked or restricted.
3. Oxidation build up on pilot electrode.
4. Wire damage to pilot assembly or bad
connection at gas valve.
5. Low gas pressure.
1. Pressure switch tubing kinked or blocked.
2. Blocked pressure tap on switch or blower.
3. Faulty pressure switch.
1. Vent blockage or improper vent
configuration.
2. Pressure switch tubing kinked or blocked.
3. Faulty pressure switch.
4. Blower not spinning up to speed.
5. Blower temp or exhaust temp too high.
6. Faulty blower temperature switch.
1. Temperature sensor out of calibration.
2. Faulty gas control.
3. Plumbing leak.
1. Pilot valve stuck in open position.

Troubleshooting

Service Procedure
Turn power on.
Normal operation.
Adjust thermostat to
temperature level.
Normal operation.
Adjust thermostat to
temperature level.
Page 17
Procedure II
Page 18
Procedure III
1. Check vent or vent
tables.
2. & 3. Page 18
4. Page 20
5. & 6. Page 22
1. Page 22
2. Replace gas
control, page 26
Replace gas control,
page 26
13
13