Watt Stopper DW-200 Installation Instructions Manual

Watt Stopper DW-200 Installation Instructions Manual

Dual technology wall switch occupancy sensors

Advertisement

Quick Links

DW-100/DW-100-347/DW-200
DW-100
SPECIFICATIONS
Voltages:
DW-100 & DW-200 ............................................120/277VAC, 50/60Hz
DW-100-347 .............................................................347VAC, 50/60Hz
Load Limits for each relay:
@120VAC .................................... 0-800W tungsten or ballast, 1/6 HP
@277VAC ...................................................................0-1200W ballast
@347VAC ...................................................................0-1500W ballast
Load Type Compatibility:
Incandescent, fluorescent, magnetic or electronic ballast
Horsepower Rating (each relay) ...............................1/6 HP @120VAC
Time Delay Adjustment ................................................... 5 to 30 minutes
Walk-Through Mode ....................3 minutes if no activity after 30 sec.
Test Mode ........................... 5 sec. for 10 min. with DIP switch setting
PIR Adjustment................................................... High or Low (DIP switch)
Ultrasonic Adjustment .................... Minimum to Maximum (trimpot), Off
Frequency.....................................................................................40kHz
Light Level Adjustment ........................................................ 8fc to 180+fc
Alerts .......................................................................... Selectable Audible
Dual Technology Wall Switch
DW-100-347
Occupancy Sensors
DW-200
US Patents: 5640113, 6617560
Santa Clara, CA 95050
v3
800.879.8585

Advertisement

Table of Contents
loading

Summary of Contents for Watt Stopper DW-200

  • Page 1 Dual Technology Wall Switch Occupancy Sensors DW-200 DW-100 DW-100-347 SPECIFICATIONS Voltages: DW-100 & DW-200 ..........120/277VAC, 50/60Hz DW-100-347 .............347VAC, 50/60Hz Load Limits for each relay: @120VAC ........0-800W tungsten or ballast, 1/6 HP @277VAC ..............0-1200W ballast @347VAC ..............0-1500W ballast Load Type Compatibility: Incandescent, fluorescent, magnetic or electronic ballast Horsepower Rating (each relay) .......1/6 HP @120VAC...
  • Page 2 OFF until light levels drop, even if the area is occupied. In the DW-200, light level only affects the load on Relay 2. Users can overrule this function by pressing the ON/OFF button. See Light Level Adjustment.
  • Page 3: Time Delay 1

    Time Delays The DW sensor holds the load ON until no motion is detected for the selected time delay. Select the time delay using DIP switch settings. In the DW-200, both relays use the same delay. Test/20 min A Test Mode with a short time delay of five seconds is set when DIP switches 1 &...
  • Page 4: Trigger Mode Standard

    Trigger Mode The DW sensor has four occupancy trigger options, set with DIP switches 5 and 6. Determine the appropriate option using the Trigger matrix. In the Trigger Mode DIP switch setting table, in order to deem the area occupied: •...
  • Page 5 Black Primary Load Primary Line Black Load Line 2 Blue Blue Brown Secondary Brown Secondary Neutral White Neutral White Load Load Green Ground Green Ground White Neutral DW-200 Bi-Level Wiring DW-200 Dual Circuit Wiring Visit our website for FAQs: www.wattstopper.com...
  • Page 6: Table Of Contents

    Test/20 min Disabled 5 minutes 15 minutes Relay 1 On Mode 30 minutes Walk-Through Audible Alerts Manual On PIR Sensitivity Auto On Walk-Through DW-200 only: Enabled Trigger Relay 2 On Mode Disabled Mode Manual On Standard Both Either Either(5) Auto On...
  • Page 7: Factory Settings

    2. Put the sensor into TEST mode. You have 5 minutes to complete the procedure. 3. Press and hold the ON/OFF button (Relay 1 button on the DW-200) for 3 seconds, until you hear a beep. 4. Step away from the sensor. After 25 seconds a beep sounds, indicating that the threshold level is set.
  • Page 8 2. Check the wire connections, in particular, the Neutral and Line connections. Verify that connections are tightly secured. 3. If lights still do not turn ON, call 800.879.8585 for technical support. Lights do not turn OFF 1. There can be up to a 30 minute time delay after the last motion is detected. To verify proper operation, set DIP switch 1 to ON, then reset switches 1 and 2 to OFF to start Test Mode.