Sizing data
Table 11C Sizing Chart _ 60 - 160
DOMESTIC WATER INLET‐
BOILER WATER INLET TEMP 
OUTLET (°F)
(°F)
165
170
180
190
200
210
220
NOTE: Highlighted items are limited by the maximum flow velocity through the piping.
Indirect Plate Water Heater Installation & Service Manual
(continued)
APW MODEL
FLOW (GPM)
APW015DW
9
APW030DW
15
APW050DW
21.5
APW070DW
33
APW090DW
42
APW105DW
52
APW120DW
62
APW015DW
12
APW030DW
19.5
APW050DW
27.5
APW070DW
42
APW090DW
53
APW105DW
66
APW120DW
78
APW015DW
16.5
APW030DW
27
APW050DW
36
APW070DW
56
APW090DW
71
APW105DW
89
APW120DW
104
APW015DW
20.5
APW030DW
33
APW050DW
44
APW070DW
68
APW090DW
87
APW105DW
109
APW120DW
126
APW015DW
24.5
APW030DW
39
APW050DW
51.5
APW070DW
80
APW090DW
101
APW105DW
127
APW120DW
147
APW015DW
28.5
APW030DW
44.5
APW050DW
58.5
APW070DW
80
APW090DW
115
APW105DW
145
APW120DW
160
APW015DW
32
APW030DW
50
APW050DW
65.5
APW070DW
80
APW090DW
128
APW105DW
160
APW120DW
160
DOMESTIC 
PRESSURE LOSS (PSI)
MAX. FLOW (GPM)
1
75
1
75
1
75
1
130
1
160
1
225
1
225
1
75
1
75
1
75
2
130
1
160
1
225
1
225
1
75
1
75
1
75
2
130
1
160
1
225
1
225
1
75
1
75
2
75
3
130
1.5
160
1
225
1.5
225
1
75
1
75
2
75
3
130
1.5
160
1
225
2
225
1
75
2
75
2
75
3
130
1.5
160
2
225
2
225
1
75
2
75
2
75
3
130
1
160
2
225
2
225
BOILER
MAX. PRESSURE LOSS (PSI)
OUTLET TEMP (°F)
152
8
144
8
135
8
139
14
138
9
141
15
137
15
154
8
143
8
132
8
137
14
136
9
140
15
134
15
157
8
143
8
130
8
135
14
134
9
139
15
132
15
162
8
144
8
129
8
136
14
134
9
140
15
132
15
166
8
146
8
128
8
136
14
135
9
141
15
132
15
170
8
148
8
129
8
146
14
135
9
143
15
136
15
175
8
150
8
129
8
156
14
136
9
146
15
146
15