Mac-21 Specifications Iii-1 - ETI PI-6000 Instruction Manual

Primary injection circuit breaker test set
Table of Contents

Advertisement

Electrical Test Instruments MAC-21
Section III – MAC-21
==============================================================================
INPUT POWER:
120 VAC, SINGLE PHASE
50/60 HZ, 20 VA Max
CURRENT RANGES:
0-1,000 / 5,000 / 25,000 / 100,000 Amperes
CURRENT ACCURACY:
+/- 0.5% Reading + 0.5% Range + 1 Digit (Continuous)
+/- 1.0% Reading + 1.0% Range + 1 Digit (Pulse > 0.01 sec)
TIMER RANGES:
0-9.999 / 0-99.99 / 0-999.9 / 0-9999 Seconds
0-999.9 / 0-9999 Cycles
TIMER ACCURACY:
+/- 0.5% of reading +/- 1 count
DIMENSIONS AND NET WEIGHT
Height:
7.0 in. (178 mm)
Width:
19.0 in. (483 mm)
Depth:
2.0 in. (51 mm)
Weight:
3.7 lb. (1.68 kg)
STANDARD ACCESSORIES
Remote Initiate cable
Contact Leads
==============================================================================
Copyright(C) 1994-2004
MAC-21 Specifications
1
S-B143
1 pair
S-A108
Electrical Test Instruments, LLC
Page III-1
All Rights Reserved