Toro DT35 Series Installation & Service Instructions Manual page 5

Rotary sprinklers

Advertisement

Connecting Hydraulic Control Tubing (Hydraulic Models Only)
1. Route control tubing from the controller
to the sprinkler location(s).
Note: Leave an 18" (45.7 cm) service
loop of tubing at each sprinkler to
facilitate movement of sprinkler and
service operations. Refer to Table 2
for tubing run length and sprinkler
elevation information.
2. Flush tubing thoroughly to remove all
air and debris.
3. Remove the tube retainer and poly cap
from the tubing adapter at the base of
the sprinkler.
4. Slide the tube retainer over the end of the control tubing and attach tubing to adapter.
5. Slide tube retainer over the adapter area to secure tubing.
System Start Up _________________________________________________________________
TO PREVENT POSSIBLE SERIOUS INJURY, DO NOT STAND OR LEAN DIRECTLY OVER ANY SPRINKLER WHEN
FILLING SYSTEM OR WHEN ACTIVATING MANUALLY AT THE SPRINKLER.
The following is a recommended procedure that will protect system components during system start-up. The procedure is based on a
velocity fill rate of less than 2' (0.61 m) per second. See Table 3 below.
1. Use jockey pump only to fill the system at a velocity fill rate of less than 2' (0.61 m) per second.
CAUTION: Failure to comply with recommended fill rate will increase line pressure resulting in a water hammer effect
that could damage sprinklers and piping components.
2. Use quick coupler keys at all tees and greens with quick coupler valves to bleed air from the system lines during the filling
process. For best results, do not compress air and then relieve it – bleed the air continuously while filling the system.
3. After water has filled all lines and all air is removed, remove the quick coupler keys.
Table 3: Recommended System Fill Rate
Pipe Size
Flow
in.
cm
GPM
1/2
1.3
2
3/4
1.9
3
1
2.5
5
1-1/4
3.1
10
1-1/2
3.8
10
2
5.0
20
2-1/2
6.4
30
Table 2: Hydraulic Control Systems
Type of System*
Normally Open (01)
with 3/16" Control Tubing
Normally Open (01)
with 1/4" Control Tubing
*• All hydraulic connections on Toro valves are
• Control line pressure must be equal to or greater than mainline pressure.
• Control line pressure range is 40 to 150 PSI.
WARNING
Velocity
LPM
ft/sec
m/sec
7.6
1.60
0.49
11.4
1.92
0.59
18.9
1.50
0.46
37.9
1.86
0.57
37.9
1.41
0.43
75.7
1.80
0.55
113.6
1.84
0.56
Maximum Distance
From Controller
500'
1000'
1
" insert type.
4
Pipe Size
Flow
in.
cm
GPM
LPM
3
7.6
45
170.3
4
10.1
75
283.9
6
15.2
150
567.8
8
20.2
250
946.3
10
25.4
450
1703.0
12
30.5
500
1893.0
Elevation Restrictions
Valve elevation should not exceed
25' ABOVE controller elevation or
70' BELOW controller elevation.
Valve elevation should not exceed
25' ABOVE controller elevation or
70' BELOW controller elevation
Velocity
ft/sec
m/sec
1.86
0.57
1.87
0.57
1.73
0.53
1.70
0.52
1.97
0.60
1.55
0.47
5

Advertisement

loading

This manual is also suitable for:

Dt55 series