Page 1
Installation Instructions & Owner's Manual IM & INT Series 12630 US Highway 33 N. Churubusco, IN 46723 Phone: (260) 693-1972 Fax: (260)693-0602 www.sterlingwatertreatment.com...
PREINSTALLATION INSTRUCTIONS FOR DEALERS: The manufacturer has set the water treatment unit's sequence of cycles, cycle times, salt dose, exchange capacity and gallon capacity. The salt dose refill time has been preset. The dealer should read this page and guide the installer regarding hardness, day override, and time of regeneration, before installation: For the installer, the following must be used: ●...
Page 4
1. Normal Operation Position: The inlet and outlet handles point in the direction of flow indicated by the engraved arrows on the control valve. Water flows through the control valve for normal operation of a water softener or filter. During the regeneration cycle this position provides regeneration water to the unit, while also providing untreated water to the distribution system (Fig.
INSTALLATION: GENERAL INSTALLATION & SERVICE WARNINGS The control valve, fittings and/or bypass are designed to accommodate minor plumbing misalignments. There is a small amount of "give" to properly connect the piping but the water softener is not designed to support the weight of plumbing. Do not use Vaseline, oils, other hydrocarbon lubricants or spray silicone anywhere.
Page 6
6. INLET/OUTLET PLUMBING: Be sure to install Bypass Valve onto main control valve before beginning plumbing. Make provisions to bypass outside hydrant and cold hard water lines at this time. Install an inlet shutoff valve and plumb to the unit's bypass valve inlet located at the right rear as you face the unit.
PROGRAMMING PROCEDURES FOR WATER SOFTENERS: 1. Set time of day: Time of day should only need to be set after extended power outages or when daylight saving time begins or ends. If an extended power outage occurs, the time of day will flash on and off indicating that the time should be reset.
Page 8
2. Programming cont'd: STEP 4 -- Regeneration Hour: The manufacturer has factory set 2:00 a.m. as the default. This is the hour of day for regeneration and can be reset by using buttons. "AM/PM" toggles after 12. The default time is 2:00 a.m. (recommended for a normal household).
OPERATING DISPLAYS FOR WATER SOFTENERS: 1. General Operation: When the system is operating, GENERAL OPERATION DISPLAYS one of the three displays may be shown. Pressing NEXT will alternate between displays. One of the displays is always the current time of day. The second display shows the current treated water flow rate through the system in Gallons Per Minute.
START-UP INSTRUCTIONS FOR WATER SOFTENERS: ● After installation is complete, rotate bypass handles to bypass mode (see Fig. 2 on page 4). ● Turn on water and check for leaks. ● Fully open a cold water faucet -- preferably a laundry sink or bathtub with no aerator. ●...
TROUBLESHOOTING GUIDE - SOFTENERS AND FILTERS: PROBLEM CAUSE CORRECTION Timer does A. transformer unplugged A. reconnect transformer not display B. no power at outlet B. repair or use working outlet time of day C. defective transformer C. replace transformer D. defective PC board D.
Page 12
PROBLEM CAUSE CORRECTION A. motor not operating A. replace motor B. no power at outlet B. repair outlet or use working outlet C. defective transformer C. replace transformer Valve stalled in D. defective PC board D. replace PC board regeneration E.
Page 15
Drive Assembly, IM Series CV3186 Power Cord with Transformer, Clack Impression Valve CV3003 Meter and Cable Assembly CV3006 Bypass Valve, IM Series, less I/O fittings CV3175CC-01GR Gray Front Cover, IM Series CV3107-01 Drive Motor, IM Series CV3108CC Circuit Board, IM Series Valve...
Page 17
INSTALLATION FITTING ASSEMBLIES: 3/4" COPPER Q-TITE CONNECTOR Item Part Description QT-34 KIT Fittings, Items # 1-3 CV3105 O-ring 215 CV3151 Nut, 1" quick connect PEX-L PEX tubing insert Loosens Drain Nut In Polytube Applications Loosens Injector and Bypass Caps SERVICE WRENCH - CV3193 Although no tools are necessary to assemble or disassemble the valve, the Service Wrench, (shown in various positions on the valve) is...
QUICK REFERENCE GUIDE: MANUAL REGENERATION GENERAL OPERATION CAPACITY REMAINING NOTE: For softeners, if When the system is operating, brine tank does not con- one of three displays will be tain salt, fill with salt and shown: Time of day, gallons wait at least 1.5 hours before per minute, or gallons of regeneration.
TEN YEAR LIMITED WARRANTY WARRANTY — First Sales, LLC warrants this water conditioner against any defects that are due to faulty material or workmanship during the warranty period. This warranty does not include damage to the product resulting from accident, neglect, misuse, misapplication, alteration, installation or operation contrary to printed instructions, or damage caused by freezing, fire, flood, or Acts of God.
Need help?
Do you have a question about the IM Series and is the answer not in the manual?
Questions and answers
I need to replace a missing locking pin (slide) for the regen operation Can I get a replacement part? How Much??
I am missing the regen locking pin. It I don't have it the hose will blow off