Bosch QV Series Installation, Operation And Maintenance Manual page 37

Table of Contents

Advertisement

QV Series Heat Pumps
Problem
Cooling
NO
COMPRESSOR
OPERATION
BUT FAN RUNS
(CONTINUED)
X
QV Series Heat Pumps
Unit Troubleshooting
Mode
Check
Heating
Is the Fault
LED
X
blinking two
(2) times?
Is the Fault
LED
X
blinking three
(3) times?
Is the Fault
LED
blinking four
(4) times?
Subject to change without prior notice
Possible
Cause
Low pressure
Check water valves and/or pumps for
fault—No or
proper operation. Check for water coil
low air flow
blockage.
75 Unit
Check for proper flow rate and water
temperature, but low-water-side temp
rise in cooling.
Low pressure
Check refrigerant pressure with a
fault—Low
gauge set.
refrigerant
Freeze fault,
Check water valves and/or pumps for
water coil—
proper operation. Check for water coil
No or low
blockage.
water flow
Freeze fault -
Check water temperature - is it
low
below 40° F entering? If heat pump
water
is connected to a closed loop with
temperature
antifreeze check that the "FREEZE 1"
resistor on the UPM board has been
cut to set the unit to antifreeze mode
(see UPM features on page #27).
Freeze fault -
Check refrigerant pressure with a
low
gauge set.
refrigerant
Condensate
Check condensate pan for high water
fault—Poor
level. Check drain line for blockages,
drainage
double trapping or inadequate
trapping.
Condensate
Check air filter and return air
fault—blocked
duct work for blockage. Check that
return air
there is adequate space
between the return air opening and
walls or other obstructions on free
return applications.
Troubleshooting | 37
Action
8733829041 (2021/07)