Trane SINTESIS ADVANTAGE CGAF Series Installation Operation & Maintenance page 29

Air-cooled scroll chillers, air to water scroll heat pumps
Hide thumbs Also See for SINTESIS ADVANTAGE CGAF Series:
Table of Contents

Advertisement

Table 7 – General data CXAF 080-110 High Efficiency (continued)
Single pump - High head pressure option
Max available Head Pressure
Motor Power
Rated Amps
Twin pump - Standard head pressure
option
Max available Head Pressure
Motor Power
Rated Amps
Twin pump - High head pressure option
Max available Head Pressure
Motor Power
Rated Amps
Expansion Tank Volume
Max User water loop Volume for
factory mounted expansion tank (1)
Optional water Buffer tank volume
Antifreeze Heater without pump
package and without buffer tank
Antifreeze Heater with pump package
and without buffer tank (Single Water
Pump digit 24=2 or 4 / Dual Water
Pump digit 24=1 or 3)
Antifreeze Heater with pump package
and with buffer tank (Single Water
Pump digit 24=2 or 4 / Dual Water
Pump digit 24=1 or 3)
Antifreeze Heater with pump package
and with buffer tank
(Single Water Pump digit 24=2 or 4 /
Dual Water Pump digit 24=1 or 3)
Condenser
Type
Quantity of coil
Face area per circuit
Condenser Fan
Quantity
Diameter
Digit 56=1
Fan / motor Type
Airflow per fan
Max Power Input per Motor
Max Amps per Motor
Motor RPM
Digit 56=2
Fan / motor Type
Airflow per fan
Max Power Input per Motor
Max Amps per Motor
Motor RPM
Digit 56=3
Fan / motor Type
Airflow per fan
Max Power Input per Motor
Max Amps per Motor
Motor RPM
Dimensions
Unit Length
Unit Width
Std Unit Height
Pump Package Option - (Additional
length configuration)
CG-SVX039C-GB
CXAF
CXAF
80
90
SHE
SHE
(kPa)
266
254
(kW)
11.0
11.0
(A)
20.8
20.8
(kPa)
153
141
(kW)
5.5
5.5
(A)
11.0
11.0
(kPa)
266
254
(kW)
11
11
(A)
20.8
20.8
(l)
50
50
(l)
1750
1750
(l)
607
607
(W)
420
420
(W)
1060/1120
1060/1120
(W)
1940/2000
1940/2000
1940/
1940/
(W)
2000
2000
#
6
6
(m²)
6.97
6.97
#
6
6
(mm)
m3/h
18087
18030
Kw
1.4
1.4
A
2.8
2.8
(rpm)
900
900
m3/h
17390
18399
Kw
1.55
1.55
A
2.5
2.5
(rpm)
870
920
m3/h
17675
18788
Kw
1.82
1.82
A
2.9
2.9
(rpm)
810
860
(mm)
3395
3395
(mm)
2200
2200
(mm)
2526
2526
(mm)
562
562
CXAF
CXAF
100
80
SHE
HE
252
266
11.0
11.0
20.8
20.8
137
153
5.5
5.5
11.0
11.0
252
266
11
11
20.8
20.8
50
50
1750
1750
607
607
420
420
1060/1120
1060/1120
1060/1120
1940/2000
1940/2000
1940/2000
1940/
2040/
2000
2100
Fin-tube heat exchanger
6
8
6.97
9.3
6
8
800
Fixed speed AC motor
17969
16801
1.4
1.4
2.8
2.8
900
910
Variable speed EC small motor
18976
15370
1.55
1.55
2.5
2.5
950
770
Variable speed EC strong motor
19194
15450
1.82
1.82
2.9
2.9
880
710
3395
4520
2200
2200
2526
2526
562
562
General Data
CXAF
CXAF
CXAF
90
100
110
HE
HE
HE
254
252
242
11.0
11.0
11.0
20.8
20.8
20.8
141
137
166
5.5
5.5
7.5
11.0
11.0
14.4
254
252
242
11
11
11
20.8
20.8
20.8
50
50
50
1750
1750
1750
607
607
607
420
420
520
1060/1120
1060/1120
1940/2000
2040/2100
2040/
2790/
2790/
2100
2850
2850
8
8
8
9.3
9.3
9.29
8
8
8
16756
16707
18042
1.4
1.4
1.13
2.8
2.8
2.2
910
910
900
15751
16766
17984
1.55
1.55
1.55
2.5
2.5
2.5
790
840
900
15871
16989
18098
1.82
1.82
1.82
2.9
2.9
2.9
730
780
830
4520
4520
4520
2200
2200
2200
2526
2526
2526
562
562
562
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents