S9361A207X INTEGRATED BOILER CONTROLLERS
Table 6. 7-Segment LED Display - Installer Mode Options. (Continued)
3-Digit 7-Segment Display
1st
Screen
2nd Screen
tP1
<Value of Test Parameter
1>
tP2
<Value of Test Parameter
2>
tP3
<Value of Test Parameter
3>
tP4
<Value of Test Parameter
4>
3-Digit 7-Segment Display
1st
Screen
2nd Screen
StA
<State number>
bt
<Sensed temperature>
SP
<Operating Setpoint>
HL_
<High Limit>
HdF
<High Limit Differential>
tt
On
OFF
or
dh
On
OFF
or
FLA
<Flame Current>
run
<Run Time Hours>
CyC
<Boiler Cycles>
Err
<Error number>
69-2751—05
3rd
Screen
Default
0
4
F
45
°
or
C
°
F
20
°
or
C
°
Table 7. 7-Segment LED Display - Reading Mode Options.
3rd
Screen
Status
F
Boiler Temperature
°
or
C
°
F
Operating Setpoint, the lowest of the IQ Outdoor air reset
°
or
C
EnviraCOM message (Desired Boiler Setpoint), high-limit
°
setpoint and setpoint from the remote user interface device.
F
Adjust High Limit Setting
°
or
C
°
F
Adjust High Limit Differential
°
or
C
°
Heat Request Status
Heat Request Status
uA
Flame Current
hr
Run Time Hours (when the boiler is heating). Shows 1 for the first
hour and 999-999 (two consecutive displays) for the 999,999th
hour. After this the counter starts over at 1.
Boiler Cycles. Shows 1 for the first cycle and 999-999 (two
consecutive displays) for the 999,999th cycle. After this the
counter starts over at 1.
Error. (See Table 9). Error screen is displayed when an error is
active (that is, in Error mode).
Range
0 to 20 minutes
The lower range of the parameter
Pump Pre-Purge Time (see above).
The parameter might be optionally
adjustable (e.g. in engineering
samples). It is currently disabled.
2 to 20 minutes
Freeze Protection Circulator Time.
The parameter might be optionally
adjustable (e.g. in engineering
samples). It is currently disabled.
40 to 75 °F
Boiler Water Freeze Temp. The
parameter might be optionally
adjustable (e.g. in engineering
samples). It is currently disabled.
5 to 160 °F
Boiler Water Freeze Temp
Differential. The parameter might
be optionally adjustable (e.g. in
engineering samples). It is currently
disabled.
Description
10
Description