Outdoor Check Function - Carrier 40QSM009DS Service Manual

Light commercial inverter side discharge cdu type
Table of Contents

Advertisement

Outdoor check function

N
00
Normal display
01
Indoor unit capacity demand code
02
Amendatory capacity demand code
The frequency after the capacity requirement
03
transfer
04
The frequency after the frequency limit
05
The frequency of sending to 341 chip
Indoor unit evaporator outlet temp.(heating T2,
06
cooling T2B)
07
Condenser pipe temp.(T3)
08
Outdoor ambient temp.(T4)
09
Compressor discharge temp.(T5)
10
AD value of current
11
AD value of voltage
12
Indoor unit running mode code
13
Outdoor unit running mode code
14
EXV open angle
15
Frequency limit symbol
Display
Display running frequency, running state or malfunction
code
Actual data*HP*10
If capacity demand code is higher than 99, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show "5.0",it means the capacity demand
is 15. the digital display tube show "60",it means the
capacity demand is 6.0)
If the temp. is lower than 0 degree, the digital display tube
will show "0".If the temp. is higher than 70 degree, the digital
display tube will show "70".
If the temp. is lower than -9 degree, the digital display tube
will show "-9".If the temp. is higher than 70 degree, the
digital display tube will show "70". If the indoor unit is not
connected, the digital display tube will show: "――"
The display value is between 13~129 degree. If the temp. is
lower than 13 degree, the digital display tube will show
"13".If the temp. is higher than 99 degree, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show "0.5",it means the compressor
discharge temp. is 105 degree. the digital display tube show
"1.6",it means the compressor discharge temp. is 116
degree)
The display value is hex number.
Off:0, Fan only 1,Cooling:2, Heating:3
Off:0, Fan only 1,Cooling:2, Heating:3, Forced cooling:4
Actual data/4.
If the value is higher than 99, the digital display tube will
show single digit and tens digit.
For example, the digital display tube show "2.0",it means the
EXV open angle is 120×4=480p.)
Frequency limit caused by
Bit7
IGBT radiator
Frequency limit caused by
Bit6
PFC
Bit5
Frequency limit caused by T4.
89
Remark
The display value is
hex
number.
example, the digital
display tube show
2A,
then
For
Bit5=1,