Viessmann Vitocrossal 300 Service Instructions Manual page 22

Gas fired condensing boiler with matrix−compact gas burner, for open flue and balanced flue operation
Hide thumbs Also See for Vitocrossal 300:
Table of Contents

Advertisement

Initial start−up, inspection and maintenance
Further details regarding the individual steps
Burner installation
1. Insert the burner and secure nuts
(6 × M 6) by hand.
Then tighten diagonally to 3 Nm.
2. Secure the gas connection pipe
with a new gasket.
¨ Safety instructions
Carry out a leak test.
Checking all gas equipment for leaks at operating pressure
¨ Safety instructions
Carry out a leak test.
1. Insert new gaskets in all fittings
that have been opened.
2. Open the gas shut−off valve.
Checking the mixer
1. Remove the motorised lever from
the mixer handle.
2. Check the mixer for ease of
operation.
22
for ease of operation and leaks
(if installed)
(cont.)
3. Push plugs fA and lÖ onto the
burner control unit.
3. Check all joints for leaks.
4. Start up the burner.
3. Check the mixer for leaks.
Replace the O rings if the mixer
leaks.
4. Snap the motorised lever into
place again.