Further details regarding the individual steps

Checking burner gauze assembly

B A
Initial start−up, inspection and maintenance
D
C
E
A
(cont.)
Replace the burner gauze assembly if
the wire mesh is damaged.
1. Remove ignition and ionisation
electrodes A.
2. Turn thermal insulation ring B
clockwise and remove carefully.
3. Slacken eight Torx screws C, and
remove burner gauze assembly D
and assembly gasket E.
4. Insert a new burner gauze
assembly D with new assembly
gasket E, and secure with eight
Torx screws.
Torque: 4.5 Nm
5. Refit thermal insulation ring B
and ignition and ionisation
electrodes A.