Installation sequence
Vitocell with fitted Solar-Divicon

Installing Solar-Divicon

Solar-Divicon installation instructions
!
Please note
Wiring can be damaged if exposed to hot com-
ponents.
Ensure adequate thermal insulation between
cables and hot pipework.
3.
2.
Fig.16

Connecting the Solar-Divicon on the solar side and checking for leaks

!
Please note
Once the thermal insulation and thermal insula-
tion cover are in place, the fittings are no longer
visible.
Carry out the following steps before fitting the
thermal insulation.
20
(cont.)
1.
Solar side
Permissible temperature
Permissible operating pressure
Test pressure
Note
For connection locations, see page 6.
140 °C
10 bar
(1 MPa)
16 bar
(1.6 MPa)