INSTRUCTIONS FOR MODELS
SEF-18100
SEF-18200
SEF-18100-8
SEF-18200-8
®
EYESAVER
Sensor Faucet
* YOUR FAUCET MAY DIFFER IN APPEARANCE
TO ITEM SHOWN, IT WILL INSTALL WITH IN
THE SAME MANNER.
For additional assistance or service please contact:
SPEAKMAN
®
800-537-2107
customerservice@speakman.com
www.speakman.com
92-SEF-18100-01
3
This Faucet has a integral swivel feature. Verify sweep of Faucet Spout and align properly before securing
Faucet Spout into final position.
NOTE: The SPEAKMAN logo
at the base of the faucet
6
Place the Solenoid Assembly against the desired mounting surface while ensuring adequate clearance for
servicing of all connections. If using the optional A/C Adapter, consider the distance to the nearest electrical
outlet. Solenoid Assembly should be mounted so the inlet and outlet ports are aligned vertically. Mark location
of Solenoid Assembly on the mounting surface using a pencil.
TOOLS AND SUPPLIES
Phillips
Adjustable
Screwdriver
Wrench
Pencil
Supply
Hoses
Drill & Drill Bit
Mounting Hardware
IMPORTANT
•
The supply line for the eyewash shall provide an
uninterruptible supply of flushing fluid at a minimum of
30 psi flowing pressure. If shut off valves are installed in
the supply line of the eyewash, provisions shall be
made to prevent unauthorized shut off. ANSI Z358.1
requires that all emergency equipment shall be tested
weekly to verify proper operation and inspected
annually to assure conformance with ANSI Z358.1
requirements.
• Do not over-tighten any connections or damage may
occur.
• Be sure to read instructions thoroughly before
beginning installation.
•
This faucet has an operating range of 20-80 psi.
•
This installation manual covers several models.
While the appearance of your faucet may vary, the
installation steps required are the same as shown in
this manual.
SAFETY TIPS
Cover your drain to prevent loss of parts. Be sure to
wear eye protection while cutting pipe.
WARRANTY
Warranty information can be found at:
www.speakman.com
should be facing front when installed properly.
10-7/8"
(275mm)
MAX
LEFT OR RIGHT
OF CENTER
9-7/16"
(240mm)
MAX
1
Ensure water supplies are shut OFF. Remove existing faucet spout and clean mounting surface. Verify that the
Rubber Gasket (1) is in position and aligned to the base of the Faucet Spout. Place Hoses and Sensor Wires
carefully, one at a time, through hole in mounting surface. Lower Faucet Spout into position.
Aerator
Wrench
(Included)
5 Gallon
Bucket
2
From below, install Rubber Mounting Washer (1), Metal Mounting Washer (2), and Mounting Nut (3).
4
Align Mounting Nut (1) so the Mounting Nut
Screws (2) are aligned towards the front and
rear of faucet as shown below. Final tighten
Mounting Nut Screws (2) using a Phillips
Screwdriver.
FRONT
7
Remove Mounting Bracket (1) from Solenoid Assembly. Using the previously marked location on mounting
surface, align Mounting Bracket (1) horizontally to approximate position and mark the mounting locations with a
pencil. If mounting on drywall and not to stud, use the appropriate anchors and fasteners for application.
Recommend screw in easy anchor or equal for drywall.
If installing with an
optional deck plate,
please place hoses and
wires through deck plate
5
Install one end of the Included Flex Hose (1) to
the Female Inlet (2) of the faucet. Install the
remaining end of the Included Flex Hose to the
OUTLET of the Solenoid (3). Wrench tighten.
REAR
NOTE:
first.
IMPORTANT
Dry Connection Only!
Do not use any
sealant on this
connection