Further details regarding the individual steps

To obtain optimum combustion values, it is essential to adjust the burner with
the boiler heated to operating temperature (min. 60 ºC).
System start−up
A
B
C
Initial start−up, inspection and maintenance
Boiler control unit service
instructions
Please note:
The Vitoflame 200 oil burner features
very good combustion values, which
are achieved without the use of fuel
oil additives (combustion
improvers). The use of combustion
improvers, which leave residues, is
not acceptable.
1. Check whether the flame tube
extension (for 15 to 33 kW) has
been fitted.
2. Check the heating system pressure
and the oil level in the tank.
3. Open the shut−off valves in the oil
supply lines on the oil tank and on
the filter.
4. Fill the oil suction line and the
filter with fuel oil using a manual
oil suction pump before switching
the burner ON.
5. Switch ON the mains electrical
isolator (outside the installation
room).
6. Switch ON system ON/OFF
switch B on the control unit.
If fault indicator lamp A on the
control unit illuminates, press
reset button C on the burner.