Burner Connections On The Gas Side - Viessmann Vitocrossal 100 Installation Instructions For Contractors

Gas condensing boiler with matrix cylinder burner open flue and room sealed operation
Table of Contents

Advertisement

Burner connections on the gas side

Note
We recommend that you use the Viessmann gas sup-
ply pipe (accessories).
1. Connect the gas supply according to TRGI 2008
[or local regulations].
Connect the gas supply according to ÖVGW-
a
TR Gas 2009 and the regionally applicable
Building Regulations.
Connect the gas supply according to SVGW.
c
Gas supply pressure: 20/25 mbar (2/2.5 kPa)
Max. permiss. gas supply pressure: 30 mbar
(3 kPa)
Gas connection:
Boiler size
80 kW
120 to 318 kW
!
Please note
Mechanically loaded gas supply pipes lead
to leaks and appliance damage.
When undoing or tightening gas connec-
tions, counterhold with a second open-
ended spanner.
Ensure all gas connections are kept free of
load and torque stress.
2. Carry out a tightness test.
Note
Only use suitable and approved leak detection
agents (EN 14291) and devices for the tightness
test. Leak detection agents with unsuitable constit-
uents (e.g. nitrites, sulphides) can cause material
damage.
Remove residues of the leak detection agent after
testing.
!
Please note
Excessive test pressure will damage the
burner and gas train.
Max. test pressure 150 mbar. If a higher
pressure is required for tightness tests, dis-
connect the burner and gas train from the
main supply pipe. Undo the fitting.
Note
Just closing the gas shut-off valve is not sufficient.
There is then a risk of pressure entering the valve.
Damage due to excessive test pressure is
excluded from our warranty.
Connection
G 1
G 1
½
3. Purge the gas line.
Note
The [German] Combustion Order stipulates that ther-
mally activated shut-off equipment must be installed in
the gas supply line.
If the gas line is contaminated (e.g. old pipes with cor-
rosion products), we recommend installing a gas filter
in the supply line.
Danger
Escaping gas can lead to explosions which may
result in serious injury.
Never purge the gas line through the boiler com-
bustion chamber.
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ci1

Table of Contents