Connecting cables to UPS2000-G-3 kVA or UPS2000-G-6 kVA
with transformer (Dual-live-wire input Dual-live-wire output)
1.
Do not set the UPS to ECO mode when the system output connects to an isolated transformer.
When you install a transformer on the output side, you are advised to connect the load to the pL terminal and disable Power
2.
segment.
3.
In the case of 110 V parallel output, short-circuit L1 and L2 and short-circuit N1 and N2. Ensure that the L1 and L2 cables are
of an equal length, and N1 and N2 cables are of an equal length.
Do not use the high voltage output
port in the case of 110 V output; otherwise,
devices may be damaged.
Do not use the high voltage output
port in the case of 110 V output; otherwise,
devices may be damaged.
7
PDU
UPS
Transformer