7-2. Outline of Main Controls

1. PMV (Pulse Motor Valve) control
1) The aperture of the PMV (1, 2) is controlled between 88(44+44) to 1000 (500 + 500) pulses during
operation.
2) During cooling and heating operations, the PMV aperture is controlled by the temperature difference
between a detected temperature from a TS sensor and a saturation temperature equivalent value (TU
temperature) from a Ps sensor. (SH control).
3) The temperature difference in 2) in both cooling and heating operations is usually controlled using a 1~6K
target value.
(However control may be performed more than 6K depending on operating conditions).
4) When the cycle overheats during both cooling and heating operations, the PMV aperture is controlled
using a detection value from a TD sensor.
The normal target value is 91°C for cooling operations and 101°C for heating operations.
Sensor malfunction may cause liquid back-flow or overheating trouble in the compressor resulting in dramatic
reduction in the durable life of the compressor.
In the event of malfunction and repair of the compressor, restart operation after checking that there are no
trouble in the resistance values or the refrigerating cycle of each sensor.
2. Discharge temperature release control
1) This control lowers the revolution number of the
compressor in the event that the discharge
temperature is not reduced or in the event the
discharge temperature increases rapidly during
PMV control.
The cycle is stabilized by dividing compressor
revolution number control into units up to 0.6
rps.
2) When the detected discharge temperature is in
a trouble zone, compressor operation is stopped
and then restarted after 2 minutes 30 seconds.
A trouble count is added on each occasion the
trouble zone is detected and when the trouble is
detected 4 times, a "P03" trouble is performed.
When normal operation continues for a period of
10 minutes, the trouble count is cleared.
CAUTION
TD (˚C)
([P03] is displayed with count 4 of trouble)
115
113
105
102
Frequency slow up (Until command)
95
– 44 –
Abnormal stop
Frequency normal down
Frequency slow down
Frequency hold
According to command