Check
Outdoor
code
LED display
[P05]
[P07]
(Item without special mention Indicates part of outdoor unit.)
[Power supply trouble] Voltage failure, open phase
Check the same items as [P04] trouble.
Is there no open phase of the
power supply?
Does the supply voltage drop or rise
(AC342 to 457V)?
Replace noise filter P.C.board,
Interface P.C.board
[Heat sink overheat trouble]
Is there any looseness in the screw
stop of the motor drive element Q21
of the compressor IPDU P.C. board,
the sub heat sink, and the diode bridge?
Are radiation grease properly applied?
Does something block the
ventilation around the heat sink?
Does something block air flow
from the fan?
(Short circuit etc.)
Replace compressor IPDU P.C. board.
* When replacing compressor IPDU P.C.board,
replace the fuse.
Check and troubleshooting
YES
NO
YES
NO
YES
NO
NO
YES
– 71 –
Correct wiring
Confirmation of
electrical work etc.
Apply radiation grease
to objective, retightening
of screw
Remove blocking matter,
Short circuit improvement