(1)-3. Sensor, current, compressor operation frequency, PMV opening indication
Interface (CDB) P.C. board detected values (for example temperature and current sensor values) can be
easily checked.
∗ Temperature sensors ... TD, TE, TL, TS, TO, TH, TA, TC, TCJ
∗ Current ......................... Current sensor (CT) value detected
∗ Pressure ....................... Low pressure sensor (Ps) value detected
LED indication
D800
D801
D802
D803
(YEL)
(YEL)
(YEL)
(YEL)
: Go ON
: Go OFF
Temperature
sensor
D804
D805
(˚C)
(YEL)
(GRN)
Less than -25
-25 ~
-20 ~
-15 ~
-10 ~
-5 ~
0 ~
5 ~
10 ~
15 ~
20 ~
25 ~
30 ~
35 ~
40 ~
45 ~
50 ~
55 ~
60 ~
65 ~
70 ~
75 ~
80 ~
85 ~
90 ~
95 ~
100 ~
105 ~
110 ~
115 ~
120 ~
Sensor trouble
: flashing (1 time/sec)
Compressor
Current
frequency
(A)
(rps)
0 ~
0
2 ~
5
4 ~
10
6 ~
15
8 ~
20
10 ~
25
12 ~
30
14 ~
35
16 ~
40
18 ~
45
20 ~
50
22 ~
55
24 ~
60
26 ~
65
28 ~
70
30 ~
75
32 ~
80
34 ~
85
36 ~
90
38 ~
95
40 ~
100
42 ~
105
44 ~
110
46 ~
115
48 ~
120
50 ~
125
52 ~
130
54 ~
135
56 ~
140
58 ~
145
60 ~
150
62 or more
155 or more
– 86 –
Degree of PMV
Pressure
opening
(kg/cm²•G)
(pls)
0 ~ 39
-2 ~
40 ~ 79
-1 ~
80 ~ 119
0 ~
120 ~ 159
1 ~
160 ~ 199
2 ~
200 ~ 239
3 ~
240 ~ 279
4 ~
280 ~ 319
5 ~
320 ~ 359
6 ~
360 ~ 399
7 ~
400 ~ 439
8 ~
440 ~ 479
9 ~
480 ~ 519
10 ~
520 ~ 559
11 ~
560 ~ 599
12 ~
600 ~ 639
13 ~
640 ~ 679
14 ~
680 ~ 719
15 ~
720 ~ 759
16 ~
760 ~ 799
17 ~
800 ~ 839
18 ~
840 ~ 879
19 ~
880 ~ 919
20 ~
920 ~ 959
21 ~
960 ~ 999
22 ~
1000
23 ~
24 ~
25 ~
26 ~
27 ~
28 ~
29 or more

Hide quick links: