Rotary Switch Setting; Push Button Setting - Fujitsu AIRSTAGE K00250LW Addendum

Outdoor unit
Table of Contents

Advertisement

Figure: Terminal resistor setting
NS1 (Network segment 1)
(Set terminal resistor at outdoor units)
Terminal resistor: on
Refrigerant system1
Master unit
Terminal resistor: off
Refrigerant system2
Master unit
Refrigerant system3
Master unit
NS3 (Network segment 3)
NS2 (Network segment 2)
Terminal resistor: on
About the setting of terminal resistor
Outdoor unit (Master unit)
:on
:off
Signal amplifi er
Install
Do not install
7. 3.

Rotary switch setting

The rotary switch (REF AD) sets the refrigerant circuit address of the outdoor unit.
Confi gure the settings only on the master unit of a refrigerant system.
If multiple refrigerant systems are connected, set the rotary switch (REF AD) as
shown in the table below.
Refrigerant circuit address
0
1
2
3
4
97
98
99
Setting
Setting range
Refrigerant circuit
0–99
address
Rotary Switch (REF AD×1): Factory setting "0"
Rotary Switch (REF AD×10): Factory setting "0"
7. 4.

Push button setting

Various functions can be set when necessary.
Perform settings after all indoor units have stopped operation.
En-19
NS4 (Network
segment 4)
Rotary Switch Setting
REF AD
×10
×1
0
0
0
1
0
2
0
3
0
4
9
7
9
8
9
9
Type of switch
Setting
example
63
REF AD × 10
REF AD × 1
Table. A: List of Settings
No
Pipe length set-
ting *1
00
Pipe length means the length between master outdoor unit and the nearest
indoor unit.
Sequential start
shift *1
10
The start-up timing of outdoor unit (compressor) can be set up so that it can
delay several seconds.
This feature is useful when multiple number of outdoor units are installed and
turned on at the same time to limit the starting current.
Cooling capacity
shift *1
11
Set this item when necessary.
Heating capacity
shift *1
12
Set this item when necessary.
(Forbidden)
13
(Forbidden)
14
(Forbidden)
15
Switching between
batch stop or
emergency stop *1
This mode selects the pattern of the stop function to be operated by the exter-
nal input terminal (CN134).
• Batch stop: The stop of all indoor units connected to same refrigerant system
20
due to input signal coming from CN134.
• Emergency stop: When emergency stop is actuated, the indoor unit does not
accept the operation command from the remote controller. On the other hand,
when the emergency stop is released (no input from CN134), the air condi-
tioner does not return to the original operation until the indoor unit is turned on
by the remote controller.
Snow falling
protection fan
mode *1
22
This mode operates the fans of outdoor units in order to prevent the units from stop-
ping operation when they are covered by snow.
Interval setting
for snow falling
protection fan
23
mode *1
When the snow falling protection fan mode is set, the operation interval of the fans
of outdoor units can be selected.
High static pressure
mode
24
When installing a duct to the blow-off outlet of an outdoor unit, set the high static
pressure mode according to the static pressure of the duct to be installed.
Furthermore, use this setting if the air blow of an outdoor unit is poor, such as when
installed in a place with a low ceiling.
(Forbidden)
25
(Forbidden)
26
(Forbidden)
27
7 segment LED indicator
Setting Item
First 2
digits
Standard (131 to 213 ft)
(40 to 65 m)
Short (less than 131 ft)
(less than 40 m)
Medium (213 to 295 ft)
0
(65 to 90 m)
Long 1 (295 to 394 ft)
(90 to 120 m)
Long 2 (394 to 492 ft)
(120 to 150 m)
Normal
21 sec. Delay
1
42 sec. Delay
63 sec. Delay
Normal mode
Save energy mode
High power mode 1
1
High power mode 2
(Forbidden)
Normal mode
Save energy mode
1
High power mode 1
High power mode 2
1
1
1
Batch stop
2
Emergency stop
Valid
2
Invalid
Standard (30 minutes)
Short 1 (5 minutes)
2
Short 2 (10 minutes)
Short 3 (20 minutes)
Standard
High static pressure 1
(equivalent to 0.12in WG
(30Pa))
2
High static pressure 2
(equivalent to 0.32in WG
(80Pa))
(Forbidden)
2
2
2
Factory
setting
Last 2 digits
0
0
0
1
0
0
2
0
3
0
4
0
0
0
1
0
0
2
0
3
0
0
0
1
1
0
2
0
3
0
4
0
0
0
1
2
0
2
0
3
3
0
0
4
0
0
5
0
0
0
0
0
0
1
0
0
2
0
1
0
0
0
1
3
0
2
0
3
0
0
0
1
4
0
2
0
3
5
0
0
6
0
0
7
0
0