Password = 19 » Power On Time & ITD Time Selection
» Under Current, Over Current,
Under Voltage, Over Voltage,
Under Frequency, Over Frequency
Password = 29 » Single Phase Prevention (SPP) Short Circuit, Lock Rotor Point,
Unbalance Current, Phase Sequence,
Phase Loss
P A S
1 9
Press
Key
SET
p O N
T I M
Press
Key
SET
I T D
T I M
Press
Key
SET
U N C
E N B
Press
Key
SET
U N C
V A L
If
2 0 0
Disable
Press
Key
SET
U N C
T I M
Press
Key
SET
O V C
E N B
Press
Key
SET
O V C
V A L
5 0 0
Press
Key
SET
O V C
T R P
T I M
If
Time
O V C
Over Current
T I M
Delay Time
5
(0-999 Sec)
O V V
E N B
Enter Password = 19
Power on
Time
5
(0-99 Sec)
Initial Delay
Time
5
(0-99 sec)
Under Current
(Enable/Disable)
If Enable
Under Current
Value
(1.00 to 60.0Amp)
Under Current
Delay Time
5
(0-999 Sec)
Over Current
(Enable/Disable)
If Enable
Over Current
Value
(1.00 to 60.0Amp)
Over Current
Trip on
( Time/Curve )
Press
Key
If
SET
Curve
O V C
Over Current
C R V
Curve Value
5 0 C
(2.5C/5.0C/
Press
Key
SET
Over Voltage
(Enable/Disable)
Password = 39 » Network Selection
Password = 59 » Display Mode Selection (Hold / Scroll)
Press
&
Long Press
Long Press
PARAMETER SETTING
Press
Disable
Press
If
Disable
If
Disable
If
Disable
10C )
»
Key Together
Reset mode , Initial Trigger,Relay Fault
mode selection.
Key
Key to enter into Password
SET
SET
Press
Key
SET
If Enable
O V V
Over Voltage
v A L
Value
4 8 0
(50-550V for 3Ø3W)
Key
SET
(30-330V for 3Ø4W)
If
O V V
Over Voltage
t I M
Delay Time
5
(0-999 sec)
Press
Key
SET
U N V
Under Voltage
E N B
(Enable/Disable)
Key
SET
If Enable
U N V
Under Voltage
V A L
Value
3 8 0
(50-520V for 3Ø3W)
(30-300V for 3Ø4W)
Press
Key
SET
U N V
Under Voltage
T I M
Delay Time
5
(0-999 Sec)
Press
Key
SET
U F
Under Frequency
E N B
Enable / Disable
Press
Key
SET
If Enable
U F
Under Frequency
V A L
Value
4 5 0
(45.0 to 65.0Hz)
Press
Key
SET
U F
Under Frequency
T I M
Delay time
5
(0 to 999 sec)
Press
Key
SET
O F
Over Frequency
E N B
(Enable / Disable)
Press
Key
SET
If Enable
O F
Over Frequency
V A L
Value
5 5 0
(45.0 to 65.0Hz)
Press
Key
SET
O f
Over Frequency
T I M
Value
5
(0 to 999 sec)
Press
Key
SET
Press
key to Save & exit
SET
Page 5