Motor Protection Device
MPD-192-M1
FEATURES
User Selectable Trip Time
Auto/Manual/ZVR Reset Function
True RMS Measurement
Protection Available
Over/Under Voltage
Unbalance
Over/Under Current
Phase Loss
Over/Under Frequency
Lock Rotor Point
Phase Sequence
Single Phase Prevention
Neutral Loss
Short Circuit
TECHNICAL SPECIFICATION
INPUT:
Voltage AC
Voltage AC
30 to 300V(L - N)
Direct Voltage AC
50 to 500V(L - L)
Burden
< 0.2VA
Current AC
Current AC
4.00Amp to 125Amp
Burden
< 0.2VA
Frequency
45.0 to 65.0 Hz
DISPLAY AND KEYS:
3 Digit, 3 Line 7 Seg 0.56",
Display
RED LED
Keys
Scroll, SET, RST, INC, DEC
DIMENSION:
Size (mm)
96 (H) X 96 (W) X 54 (D) mm
Panel Cutout (mm)
92 (H) X 92 (W) mm
Under Current fault Message
1) Unc in R Phase
Fault in R phase
R
Under Current
U N C
2 8 7
R phase Current Value
2) Unc in Y Phase
3) Unc in B Phase
B
Y
U N C
U N C
2 6 3
2 7 2
4) Unc in RY Phase
5) Unc in YB Phase
R Y
Y B
U N C
U N C
2 7 0
2 6 0
6) Unc in RB Phase
7) Unc in RYB Phase
R
B
R Y B
U N C
U N C
2 5 5
2 5 5
Frequency Fault Message
Over Frequency Fault Message
Under Frequency Fault Message
Over frequency
Under frequency
O V F
U N F
Frequency Value
Frequency Value
5 2 6
4 8 6
Unbalance Fault Message
1) Unb in R Phase
Fault Between R & B Phase
R
B
U N B
Unbalance
5 5
Unbalance Percentage
Between R & B Phase
2) Unb in Y Phase
3) Unb in B Phase
Y B
R y
U N B
U N B
5 7
5 9
4) Unb in RYB Phase
R Y B
U N B
5 5
Phase Sequence Message
Phase
P H A
Sequence
S E Q
F L T
Fault
NETWORK SELECTION:
3 Phase - 4 Wire,3 Phase - 3 Wire
TRIP SETTING:
Under Current
4.00 to 125A
Over Current
4.00 to 125A
50 to 520V For 3Ø - 3W
Under Voltage
30 to 300V For 3Ø - 4W
50 to 550V For 3Ø - 3W
Over Voltage
30 to 330V For 3Ø - 4W
Over / Under Frequency
45.0 to 65.0 Hz
Short Circut
1 - 9 Scale
Lock Rotor Point
0.5 to 9.0 Scale
Unbalance
5 - 60%
TIME PARAMETER:
Power On Delay
0 to 99 Sec
Initial Time Delay
0 to 99 Sec
Trip Delay Time
(Voltage, Current, Frequency,
0 to 999 Sec
SSP, Unbalance)
Scrolling Time
1 to 99 Sec
Reset Time
0 to 99 Sec
OUTPUT SPECIFICATION:
Relay
2 Nos
st
1 Relay ( NO - C - NC )
Relay Type
2 Relay ( NO - C )
nd
1 Relay 10Amp, 250V AC
st
Rating
2 Relay 5 Amp, 250V AC
nd
AUXILIARY SUPPLY:
100 to 270V AC/DC, 50/60Hz
Supply Voltage
Power Consuption
3VA @ 230 AC MAX
ENVIRONMENTAL CONDITION:
Working Temperature
0 to 55°C
Storage Temperature
0 to 55°C
Relative Humidity
95 % RH Non-Condensing
IP-65 (Front side As per
Protection Level
(As Per request)
IS/IEC 60529 : 2001)
TERMINAL CONNECTION
20
19
18
17
16
15
14 13
S1
S2
S1
S2
S1
S2
L1
L2
L3
C
CT
NOTE
USE
PROVIDED
Relay-2
BY MULTISPAN ONLY
MPD 192-T1-E3-N8
CAT III
Range
5
Current: 4A To 125A AC
Made in India
Voltage (L-L) : 50-520V AC
100 270V
(L-N) : 30-300V AC
!
AC/DC
50/60 Hz, 3VA
Relay-1
www.multispanindia.com
NC
NO
C
L
N
V
E
L
1
1
2
3
4
5
6
7
FAULT MASSAGE
Phase Loss Message
1) R Phase loss
R
R
Phase
P H A
Loss
L O S
2) Y Phase loss
3) B Phase loss
Y
P H A
P H A
L O S
L O S
Single Phase Prevention Fault
1) SPP in R Phase
R Phase Fault
R
S P P
Single Phase Prevention
1 0 0
R - Phase Voltage Value
2) SPP in Y Phase
3) SPP in B Phase
Y
S P P
1 0 5
SPP Fault Due to Phase Loss
1) SPP in R Phase
S P P
Single Phase Prevention
R
R Phase
L O S
Loss
2) SPP in Y Phase
3) SPP in B Phase
S P P
Y
L O S
Lock Rotor Point
1) LRP in R Phase
R Phase Fault
R
Lock Rotor Point
L R P
Phase Current Value
5 0 0
2) LRP in Y Phase
3) LRP in B Phase
Y
L R P
5 0 0
Neutral Loss Message
S P P
R
1 5 8
NOTE : Neutral loss Protection available Only,
In Case Of SPP Enable
KEY OPERATION
Operator Mode
To View Individual Parameters Value
To Enter In Parameter Setting Mode
To View The Voltage Page While Display
Indicate fault
To View The Current Page While Display
Indicate fault
To Reset The Relay Contact manually after
Tripping
To Scroll & Hold For 5 Second Press
Parameter Setting Mode
Edited Parameter Value to be Set, And Move
to the Next Step
To Increment Parameter Value
To Decrement Parameter Value
MECHANICAL INSTALLATION
Outline Dimension (mm)
96
96
1. Prepare the panel cutout with proper dimensions as shown
above.
2. Fit the unit into the panel with the help of clamp given.
3. The equipment in its installed state must not come in close
proximity to any heating source, caustic vapors, oil steam,
or other unwanted process byproducts.
4. Use the specified size of crimp terminal (M3.5 screws) to
wire the terminal block. Tightening the screws on the
terminal block using the tightening torque of the range of
1.2 N.m.
12
11
5. Do not connect anything to unused terminals.
MAINTENANCE
D+
D -
NO
MODBUS
MAINTENANCE
System
1. The equipment should be cleaned regularly to avoid
3Ph-4W/3Ph-3W
blockage of ventilating parts.
Accuracy Class: 1.0
2. Clean the equipment with a clean soft cloth. Do not use
isopropyl alcohol or any other cleaning agent.
V
N
V
L
L
3. Fusible resistor must not be replaced by operator.
2
3
8
9
10
ø
3
- 4W NETWORK CONNECTION
1) V
Page
LN
R1
B
2) V
Page
LL
R1
3) Amp Page
B
S P P
1 1 0
R1
4) Frequency Page
R1
S P P
B
L O S
1) 3 Phase - 4 Wire
R
S1
S2
Y
S1
S2
B
S1
S2
B
20
19
18
17
16
15
L R P
S1
L1
S2
S1
L2
S2
S1
L3
S2
5 0 0
CT
NOTE
USE
PROVIDED
BY MULTISPAN ONLY
MPD 192-T1-E3-N8
CAT III
Range
5
Current: 4A To 125A AC
Made in India
Voltage (L-L) : 50-520V AC
100 270V
(L-N) : 30-300V AC
!
AC/DC
50/60 Hz, 3VA
Relay-1
NO
C
NC
L
N
E
1
2
3
4
5
6
!
Please read the "Safety Warnings" in the instruction
manual supplied with the instrument thoroughly and
OR
completely for correct use. Failure to follow the safety rules
can cause fire, trouble, electrical shock, etc. Therefore, make
sure to operate the instrument on a correct power supply
SET
and voltage rating marked on each
If all the equipment is not handled in a manner specified
by the manufacturer, it might impair the protection provided
by the equipment.
RST
Scroll
SET
1) To prevent the risk of electric shock, power supply to the
equipment must be kept OFF while doing the wiring
arrangement. Do not touch the terminals while power is
being supplied.
2) To reduce electro magnetic interference, use wire with
adequate rating and twists of the same of equal size shall
be made with shortest connection.
3. Cable used for connection to power source, must have a
cross section of 1mm or greater. These wires should have
insulations capacity made of at least 1.5kV.
Panel Cutout
Dimension (mm)
4) A better anti-noise effect can be expected by using
standard power supply cable for the instrument.
92
1) Do not allow pieces of metal, wire clippings, or fine
metallic fillings from installation to enter the product or
92
54
else it may lead to a safety hazard that may in turn
3
endanger life or cause electrical shock to the operator.
2) Circuit breaker or mains switch must be installed
between power source and supply terminal to facilitate
power 'ON' or 'OFF' function. However this mains switch
or circuit breaker must be installed at convenient place
normally accessible to the operator.
3) Use and store the instrument within the specified ambient
temperature and humidity ranges as mentioned in this
manual.
DISPLAY PAGES
ø
3
- 3 W NETWORK CONNECTION
1) V
Page
LL
R1
2) Amp Page
R1
3) Frequency Page
R1
WIRING CONNECTION
2) 3 Phase - 3 Wire
R
R
Y
S1
S2
B
N
14 13
12
11
20
19
S1
S2
D+
D -
L1
C
NO
MODBUS
NOTE
Relay-2
CAT III
System
3Ph-4W/3Ph-3W
Accuracy Class: 1.0
Made in India
100 270V
AC/DC
50/60 Hz, 3VA
www.multispanindia.com
L
N
V
V
V
N
L
L
L
1
2
3
1
2
7
8
9
10
SAFETY PRECAUTION
instrument.
Read complete instructions prior to installation
and operation of the unit.
WARNING : Risk of electric shock.
WARNING GUIDELINES
WARNING : Risk of electric shock.
INSTALLATION GUIDELINES
R
Y
Y
B
S1
S2
B
S1
S2
18
17
16
15
14 13
12
11
S1
S2
S1
S2
D+
D -
L2
L3
C
NO
MODBUS
CT
USE
PROVIDED
Relay-2
BY MULTISPAN ONLY
MPD 192-T1-E3-N8
Range
System
5
Current: 4A To 125A AC
3Ph-4W/3Ph-3W
Voltage (L-L) : 50-520V AC
Accuracy Class: 1.0
(L-N) : 30-300V AC
!
Relay-1
www.multispanindia.com
NC
NO
C
V
V
N
V
E
L
L
L
1
2
3
3
4
5
6
7
8
9
10
Page - 1
Need help?
Do you have a question about the MPD-192-M1 and is the answer not in the manual?
Questions and answers